(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
CC-Link/LT compatible unit for an on-panel/on-equipment wire saving network.
[Features]
· Can be used as a remote device station.
[Applications]
· Convenient for equipment connection in a field network.
Part Number
Configured Part Number is shown.
CL2X16-D1MJ1V

CL1X2-D1D3S

CL1X4-D1B2

CL1X4-D1C3

CL1X4-D1S2

CL2X8-D1B2

CL2X8-D1C3V

CL2X8-D1S2

CL2X16-D1C3V
| Ambient Operating Temperature | 0 to 55℃ | ||
|---|---|---|---|
| Ambient Storage Temperature | -25 to 75℃ | ||
| Ambient Operating Humidity | 5 to 95% RH: no condensation | ||
| Ambient Storage Humidity | 5 to 95% RH: no condensation | ||
| Vibration Resistance | Judgment Criteria | Based on IEC61131-2. | |
| Under Intermittent Vibration | Frequency: 10 To 57 Hz | Single amplitude: 0.075 mm Sweeps: 10 sweeps in each direction of X, Y and Z (80 minutes) | |
| Frequency: 57 To 150 Hz | Acceleration: 9.8 m/s2 Sweeps: 10 sweeps in each direction of X, Y and Z (80 minutes) | ||
| Under Continuous Vibration | Frequency: 10 To 57 Hz | Single amplitude: 0.035 mm Sweeps: 10 sweeps in each direction of X, Y and Z (80 minutes) | |
| Frequency: 57 To 150 Hz | Acceleration: 4.9 m/s2 Sweeps: 10 sweeps in each direction of X, Y and Z (80 minutes) | ||
| Impact Resistance | 147 m/s2, 3 times in each direction of X, Y and Z Judgment criteria are based on IEC61131-2. | ||
| Operating Atmosphere | No corrosive gas | ||
| Operating Altitude | 2,000 m or lower Cannot be used in environments pressurized higher than the atmospheric pressure, which could be created around 0 m of altitude. Doing so may cause failures. | ||
| Installation Location | Inside the control panel May be used in an environment other than inside the control panel, so long as the environment satisfies the ambient operating temperature, ambient operating humidity and other conditions. | ||
| Overvoltage Category | II or lower Indicates the assumed wiring part to which the applicable equipment is connected between the public network and the mechanical system in plant. Category II applies to the equipment to which power is supplied from a fixed facility. The surge withstand voltage for equipment of up to 300 V in rating is 2,500 V. | ||
| Pollution Degree | 2 or lower Index to indicate the degree of conductive material generation in the environment in which the applicable equipment is used. Pollution degree 2 indicates that only non-conductive contaminants will generate. However, temporary conduction may still occur in the environment due to accidental condensation. | ||
| Ambient Operating Temperature | 0 to 55℃ | ||
|---|---|---|---|
| Ambient Storage Temperature | -25 to 75℃ | ||
| Ambient Operating Humidity | 5 to 95% RH, no condensation | ||
| Ambient Storage Humidity | 5 to 95% RH, no condensation | ||
| Vibration Resistance | JIS B 3502, IEC 61131-2 compliant | Under Intermittent Vibration | Frequency: 5 to 8.4 Hz, single amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, constant acceleration: 9.8 m/s2 Sweeps: 10 sweeps in each direction of X, Y and Z |
| Under Continuous Vibration | Frequency: 5 to 8.4 Hz, Single amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m/s2 | ||
| Impact Resistance | JIS B 3502, IEC 61131-2 compliant (147 m/s2, 3 times in each direction of X, Y and Z) | ||
| Operating Atmosphere | No corrosive gas | ||
| Operating Altitude | 0 to 2,000 m | ||
| Installation Location | Inside the control panel | ||
| Overvoltage Category | II or lower | ||
| Pollution Degree | 2 or less | ||
| Part Number |
|---|
| CL2X16-D1MJ1V |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS | Number Of Inputs | Terminal Shape | Type of Unit | Input target | External connection | I/O unit power supply current |
|---|---|---|---|---|---|---|---|---|---|---|---|
- | 1 Piece(s) | Quote | 6 | 16 | MIL Connector | DC Input (Unit, I/O Power Supply Dual Use) | Positive Common | 1-line type | 45mA |
Loading...
| Rated Input Voltage(V) | DC24V | Rated input current(mA) | 4mA | Input answer time | 0.5ms / 1.5ms |
|---|
Please check the type/dimensions/specifications of the part CL2X16-D1MJ1V in the CC-Link/LT Input/Output Unit (Input) series.
| Part Number |
|---|
| CL1X4-D1B2 |
| CL1X4-D1C3 |
| CL1X4-D1S2 |
| CL2X16-D1M1V |
| CL2X8-D1B2 |
| CL2X8-D1S2 |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS | Number Of Inputs | Terminal Shape | Type of Unit | Input target | External connection | I/O unit power supply current |
|---|---|---|---|---|---|---|---|---|---|---|---|
- | 1 Piece(s) | Quote | 6 | 4 | Screw terminal block | DC input | Positive/ Negative Common | 2-Wire | 40mA | ||
MYR 1,268.80 | 1 Piece(s) | Quote | 6 | 4 | Sensor Connectors (e-CON) | DC input | Positive Common | 3-Wire | 35mA | ||
- | 1 Piece(s) | Quote | 6 | 4 | Spring Clamp | DC input | Positive/ Negative Common | 2-Wire | 40mA | ||
- | 1 Piece(s) | Quote | 6 | 16 | MIL Connector | DC input | Positive Common | 1-line type | 45mA | ||
- | 1 Piece(s) | Quote | 6 | 8 | Screw terminal block | DC input | Positive/ Negative Common | 2-Wire | 40mA | ||
- | 1 Piece(s) | Quote | 6 | 8 | Spring Clamp | DC input | Positive/ Negative Common | 2-Wire | 40mA |








MITSUBISHI
Standard Price : MYR 4,578.33
Days to Ship : 4 Day(s)
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy