Power supply adapter that can supply power to CC-Link/LT systems from an external power source.
[Features]
· Power supply adapter for general-purpose sequencer.
· Stable 24 V DC.
· Stabilizes the entire system.
[Applications]
· Power supply.
Part Number
Configured Part Number is shown.
CL1PAD1

CL1PAD1 external appearance

CL1PAD1 dimensional drawing, unit: mm
| Voltage Input Range | Max. 28.8 V DC (rated voltage 24 V DC) |
|---|---|
| Max. Rated Current | 5.0 A [Use the system so that the total current consumption of each station does not exceed the maximum rated current when power is supplied (except immediately after the power is turned on).] |
| External Connection Method | · Power supply to power supply adapter: terminal block, 3 points (M3 screw) · Power supply part to communication part and CC-Link/LT system: dedicated CC-Link/LT connector (4 pins) × 2 |
| Mass | 0.26 kg |
| Ambient Temperature | 0 to 55°C - When Operating, -25 to 70°C - When Saving | ||
|---|---|---|---|
| Relative Humidity | 5 to 95% RH (No Condensation) - When Operating / When Saving | ||
| Vibration Resistance | Under Intermittent Vibration | Frequency: 10 To 57 Hz | Single amplitude: 0.075 mm 10 times in each direction of X, Y and Z (total 80 minutes each) |
| Frequency: 57 To 150 Hz | Acceleration: 9.8 m/s2 10 times in each direction of X, Y and Z (total 80 minutes each) | ||
| Under Continuous Vibration | Frequency: 10 To 57 Hz | Single amplitude: 0.035 mm 10 times in each direction of X, Y and Z (total 80 minutes each) | |
| Frequency: 57 To 150 Hz | Acceleration: 4.9 m/s2 10 times in each direction of X, Y and Z (total 80 minutes each) | ||
| Impact Resistance | 147 m/s2, 3 times in each direction of X, Y and Z | ||
| Insulation Resistance | Between all external terminals at once and the earth terminal: 10 MΩ at 500 V DC on an insulation resistance meter | ||
| Operating Atmosphere | There shall be no corrosion gas or flammable gas and not much conductive dust. | ||
| Altitude Of Use | 2,000 m or lower Cannot be used in environments pressurized higher than the atmospheric pressure. Doing so may cause failures. | ||
| Installation Location | Inside the control panel | ||
| Overvoltage Category | II or lower Indicates the assumed wiring part to which the applicable equipment is connected between the public network and the mechanical system in plant. Category II applies to the equipment to which power is supplied from a fixed facility. The surge withstand voltage for equipment of up to 300 V in rating is 2,500 V. | ||
| Pollution Degree | 2 or lower Index to indicate the degree of conductive material generation in the use environment. Pollution degree 2 indicates that only non-conductive contaminants will generate. However, temporary conduction may still occur in the environment due to accidental condensation. | ||
| Part Number |
|---|
| CL1PAD1 |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS |
|---|---|---|---|---|---|
MYR 721.95 | 1 Piece(s) | Quote | 6 |
Loading...
| Rated Input Voltage | DC24V | Maximum Output Voltage/ Current | DC24V· 5A | Note | CL1PAD1 CC-Link/LT Power Supply Adapter (5A) - Compatible Standards: UL/cUL CE (EMC) |
|---|
Please check the type/dimensions/specifications of the part CL1PAD1 in the CC-Link/LT Power Adapter series.




How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy