(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
WS Series NF-F Type no-fuse breaker.
[Features]
· Small, high performance, and economical no-fuse breaker.
· UL and cUR compatible.
· NF30-FAU, NF50-FAU, NF50-FHU.
[Applications]
· No-fuse breaker, general-purpose product.
Part Number
Configured Part Number is shown.

NF30-FAU Circuit Breakers

NF50-FAU Circuit Breakers

NF50-FHU Circuit Breakers
| Type Circuit Breakers | No-Fuse Breaker | ||||||||
|---|---|---|---|---|---|---|---|---|---|
| Frame A | 30 | 50 | 50 | ||||||
| Type Name | NF30-FAU | NF50-FAU | NF50-FHU | ||||||
| Phase Wire System (Note 1) | - | - | - | ||||||
| Number Of Contacts | 2 | 3 | 2 | 3 | 2 | 3 | |||
| Rated Current A (Standard Ambient Temperature 40°C) | 5 10 15 20 30 | 5 10 15 20 30 40 50 | 3 5 10 15 20 30 40 50 | ||||||
| Rated Current For Motor Protection (Note 8) | 2 4 6.3 8 16 | 0.3 0.4 0.6 0.8 1.2 1.4 2 2.5 4 7.1 8 12 16 25 32 45 | |||||||
| Electrical Leakage Properties | High Speed Type | Rate Sensitivity Current I △n mA | - | - | - | ||||
| Pickup Current UL1053 | - | - | - | ||||||
| Maximum Operating Time s Or Less At 5I Δn (Note 2) | - | - | - | ||||||
| Electrical Leakage Display Method | - | - | - | ||||||
| Rated Short Circuit Breaking Capacity kA | UL 1077 CSA C22.2 No. 235 | Rated Voltage | AC (V) | 240 | 240 | 240 | |||
| DC (V) | 60 | 60 | - | ||||||
| AC | 240 V | 2.5 (Note 3) | 2.5 (Note 3) | 5 | |||||
| DC | 60 V | 1.5 | 1.5 | - | |||||
| IEC 60947-2 EN 60947-2 (Icu/Ics) | Rated Insulation Voltage (V) | 250 | 250 | 500 | |||||
| AC | 400 V | - | - | 1.5/1 | |||||
| 230 V | 2.5/1 (Note 4) | 2.5/1 (Note 4) | 5/2 | ||||||
| DC | 60 V | 1.5/1 | 1.5/1 | - | |||||
| GB 14048.2 (Icu/Ics) | Rated Insulation Voltage (V) | 250 | 250 | 500 | |||||
| AC | 415 V | - | - | 1.5/1 | |||||
| 240 V | - | - | 5/2 | ||||||
| 230 V | 2.5/1 (Note 4) | 2.5/1 (Note 4) | - | ||||||
| DC | 60 V | 1.5/1 | 1.5/1 | - | |||||
| JIS C 8201-2-1 Ann.1 Ann.2 (Icu/Ics) | Rated Insulation Voltage (V) | 250 | 250 | 500 | |||||
| AC | 415 V | - | - | 1.5/1 | |||||
| 200 V | 2.5/1 (Note 4) | 2.5/1 (Note 4) | 5/2 | ||||||
| DC | 65 V | 1.5/1 | 1.5/1 | - | |||||
| JIS C 8201-2-2 Ann.1 Ann.2 (Icu/Ics) | Rated Operating Voltage AC (V) | - | - | - | |||||
| AC | 200 V | - | - | - | |||||
| 100 V | - | - | - | ||||||
| Rated Impulse Withstand Voltage Uimp (kV) | 2.5 | 2.5 | 4 | ||||||
| Current Type | AC/DC shared | AC/DC shared | AC | ||||||
| Isolation Compliant | - | - | - | ||||||
| Reverse Connections | - | - | - | ||||||
| External Dimensions (mm) | a | 40 | 60 | 40 | 60 | 50 | 75 | ||
| b | 72 | 72 | 96 | ||||||
| c | 57 | 57 | 60 | ||||||
| ca | 73.5 | 73.5 | 76 | ||||||
| Product Mass kg | 0.14 | 0.2 | 0.16 | 0.22 | 0.25 | 0.37 | |||
| Mounting Method | IEC 35 mm Rail | ◎(Standard support for mounting IEC 35 mm rail) | ◎(Standard support for mounting IEC 35 mm rail) | ◎(Standard support for mounting IEC 35 mm rail) | |||||
| Mounting Screw (Note 5) | Possible | Possible | Possible | ||||||
| Front Plate Installation (Note 6) | Possible | Possible | - | ||||||
| Electrical Appliance And Material Safety Law | compliant | Compliant | Compliant | ||||||
| CE Mark | TÜV certification | TÜV certification | TÜV certification | ||||||
| CCC Certification | acquired | acquired | acquired | ||||||
| Overcurrent Tripping Method | Thermal | Thermal | Completely electromagnetic | ||||||
| Trip Button | -(Note 7) | -(Note 7) | -(Note 7) | ||||||
Note 1: When using a 3-contact earth leakage breaker for 1 ø 2 W, do not use the center contact. Connect the left and right contacts.
When using for 1 ø 3 W, connect the center contact to a neutral wire. (UL cannot use 1 ø 3 W.)
Note 2: 0.1 for UL1053.
Note 3: The rated breaking capacity is 1.5 kA for parts with 5 A rated current.
Note 4: The rated breaking capacity is 1.5/1 kA for parts with 5 A rated current.
Note 5: The customer must provide the mounting screws. For details, please refer to the catalog.
Note 6: Can install surface plate without tightening nuts from the back. (The customer must provide the mounting screws M5 × 0.8 × 30) Here, terminal screws can be tightened from the back of the breaker.
Note 7: Only included when an alarm switch (AL) is attached. (Excludes NF30-FAU and NF50-FAU SHT+AL)
Note 8: For rated current for motor protection, only current sensitivities of 30 mA or 50 mA can be manufactured.

| Rated Voltage | Applicable Circuit Voltage | Variable Voltage Range In Which Electrical Leakage Protection Function Can Operate |
|---|---|---|
| 100-200 V | 100/110/200/220 V | 80 to 242 V |
| 240 V (UL) | 240 V | 132 to 264 V |
| 240 V (GB) | 240 V | 204 to 264 V |
| 230 V | 240 V | 195 to 253 V |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS | Ampere frame | Number of Poles | Rated Current (A) | Dimension height (mm) | Dimension width (mm) | Dimension depth (mm) | Type | Motor breaker (Apply) | Rated block capacity AC 220 V (kA) | Rated block capacity AC 240 V (kA) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
- | 1 Piece(s) | Quote | 6 | 30AF | 2 | 5 | 72 | 40 | 73.5 | No fuse breaker (standard product) | Not applicable | - | 1.5 | ||
- | 1 Piece(s) | Quote | 6 | 30AF | 2 | 10 | 72 | 40 | 73.5 | No fuse breaker (standard product) | Not applicable | - | 2.5 | ||
MYR 171.33 | 1 Piece(s) | Quote | 6 | 30AF | 2 | 15 | 72 | 40 | 73.5 | No fuse breaker (standard product) | Not applicable | - | 2.5 | ||
- | 1 Piece(s) | Quote | 6 | 30AF | 2 | 20 | 72 | 40 | 73.5 | No fuse breaker (standard product) | Not applicable | - | 2.5 | ||
- | 1 Piece(s) | Quote | 6 | 30AF | 2 | 30 | 72 | 40 | 73.5 | No fuse breaker (standard product) | Not applicable | - | 2.5 | ||
- | 1 Piece(s) | Quote | 6 | 30AF | 3 | 5 | 72 | 60 | 73.5 | No fuse breaker (standard product) | Not applicable | - | 1.5 | ||
MYR 220.00 | 1 Piece(s) | Quote | 6 | 30AF | 3 | 10 | 72 | 60 | 73.5 | No fuse breaker (standard product) | Not applicable | - | 2.5 | ||
- | 1 Piece(s) | Quote | 6 | 30AF | 3 | 15 | 72 | 60 | 73.5 | No fuse breaker (standard product) | Not applicable | - | 2.5 | ||
- | 1 Piece(s) | Quote | 6 | 30AF | 3 | 20 | 72 | 60 | 73.5 | No fuse breaker (standard product) | Not applicable | - | 2.5 | ||
- | 1 Piece(s) | Quote | 6 | 30AF | 3 | 30 | 72 | 60 | 73.5 | No fuse breaker (standard product) | Not applicable | - | 2.5 | ||
- | 1 Piece(s) | Quote | 6 | 50AF | 2 | 20 | 72 | 40 | 73.5 | No fuse breaker (standard product) | Not applicable | - | 2.5 | ||
- | 1 Piece(s) | Quote | 6 | 50AF | 2 | 8 | 96 | 50 | 76 | No fuse breaker (high breaking capacity product) | Apply | - | 5 | ||
- | 1 Piece(s) | Quote | 6 | 50AF | 3 | 1.4 | 96 | 75 | 76 | No fuse breaker (high breaking capacity product) | Apply | - | 5 | ||
- | 1 Piece(s) | Quote | 6 | 50AF | 3 | 5 | 96 | 75 | 76 | No fuse breaker (high breaking capacity product) | Not applicable | 5 | 5 | ||
- | 1 Piece(s) | Quote | - | 50AF | 3 | 8 | 96 | 75 | 76 | No fuse breaker (high breaking capacity product) | Apply | - | 5 | ||
- | 1 Piece(s) | Quote | - | 50AF | 3 | 16 | 96 | 75 | 76 | No fuse breaker (high breaking capacity product) | Apply | - | 5 |
Loading...
| Rated block capacity, voltages except VAC 100/200/400, VDC 250 | Available | Mounting Method | DIN/Screw retention | Connection Method | Surface type |
|---|---|---|---|---|---|
| Representative Standard | PSE / CE / UL / TUV / CCC |


MITSUBISHI
Days to Ship : 16 Day(s) or more


MITSUBISHI
Days to Ship : 14 Day(s) or more




How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy