- MCCB (Molded Case Circuit Breakers) High performance class NF-HRV series from Mitsubishi electric. - Frame size is 50. - No. of pole can be select 2 or 3 poles. - Applicable for both AC/DC. - Rated ambient temperature 40°C. - Rated current can be select up to 50 A. - Rated insulation voltage (Ui) is 690 V - Mechanical duration (On/Off) is up to 25,000 times. - Electrical duration (On/Off) is up to 10,000 times. - Possible to reverse connection.
Part Number
Configured Part Number is shown.
NF63-HV 3P 10A
| Type Name Circuit Breakers | NF63-HV Circuit Breakers | |||||
|---|---|---|---|---|---|---|
| Rated current In A Standard ambient temperature 40°C (45°C for marine) | 10 15 20 30 40 50 | |||||
| Number of Positions | 2 | 3 | 4 | |||
| Rated Insulation Voltage Ui V | 690 | |||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | 2.5/2.5 | ||
| 500 V | 7.5/7.5 | |||||
| 440 V | 10/8 | |||||
| 415 V | 10/8 | |||||
| 400 V | 10/8 | |||||
| 380 V | 10/8 | |||||
| 230 V | 25/19 | |||||
| DC | 250 V (*1) | 7.5/7.5 | ||||
| GB 14048.2 (Icu/Ics) | AC | 415 V | 10/8 | |||
| 400 V | 10/8 | |||||
| 380 V | 10/8 | |||||
| 230 V | 25/19 | |||||
| DC | 250 V | 7.5/7.5 | ||||
| NK (Icu/Ics) | AC | 450 V | 10/8 | - | ||
| 240 V | 25/19 | - | ||||
| DC | 250 V | 7.5/7.5 | - | |||
*: Circuit Breakers For 3-position and 4-position products, use 2 positions.

Internal equipment of NF63-HV

Temperature correction curve of NF63-HV
| Type Name Circuit Breakers | NF63-HRV Circuit Breakers | NF125-HV Circuit Breakers | ||||||
|---|---|---|---|---|---|---|---|---|
| Rated current In A Standard ambient temperature 40°C (45°C for marine) | 15 20 30 40 50 | 15 20 30 40 50 | ||||||
| Number of Positions | 2 | 3 | 2 | 3 | 4 | |||
| Rated Insulation Voltage Ui V | 690 | 690 | ||||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | 2.5/1 | 10/8 | |||
| 500 V | 20/10 | 30/23 | ||||||
| 440 V | 30/15 | 50/38 | ||||||
| 415 V | 30/15 | 50/38 | ||||||
| 400 V | 30/15 | 50/38 | ||||||
| 380 V | 30/15 | 50/38 | ||||||
| 230 V | 85/43 | 100/75 | ||||||
| DC | 250 V (*1) | 40/20 | - | |||||
| GB 14048.2 (Icu/Ics) | AC | 415 V | - | 50/38 | ||||
| 400 V | - | 50/38 | ||||||
| 380 V | - | 50/38 | ||||||
| 230 V | - | 100/75 | ||||||
| DC | 250 V | - | - | |||||
| NK (Icu/Ics) | AC | 450 V | 30/15 | 50/38 | - | |||
| 240 V | 85/43 | 100/75 | - | |||||
| DC | 250 V | 40/20 | - | - | ||||
| Parts included as standard (Surface type) | Mounting screw M4 × 0.7 × 55 (2, 3-position 2 pcs., 4-position 4 pcs.) (*2) Insulation barrier (2-position 1 pc., 3-position 2 pcs., 4-position 3 pcs.) | |||||||
*1: Circuit Breakers For 3-position and 4-position products, use 2 positions. In that case, do not use the neutral pole of the 4-position product. Also, if you connect as shown in the figure, you can use up to 400 V DC for3-position products and 500 V DC for 4-position products. Please refer to the catalog for more details.
*2: It is attached to NF63-HRV and NF125-HV.

Internal equipment of NF63-HRV/NF125-HV
* Circuit Breakers For 2-position products of NF63-HRV and NF125-HV, refer to the number of mounting of 3-position products.

Temperature correction curve of NF63-HRV/NF125-HV
| Type Name Circuit Breakers | NF125-HEV Circuit Breakers | ||||
|---|---|---|---|---|---|
| Rated current In A Standard ambient temperature 40°C | 50 | ||||
| Number of Positions | 3 | 4 | |||
| Rated Insulation Voltage Ui V | 690 | ||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | 10/8 | |
| 500 V | 50/38 | ||||
| 440 V | 65/65 | ||||
| 415 V | 70/70 | ||||
| 400 V | 75/75 | ||||
| 380 V | 75/75 | ||||
| 230 V | 100/100 | ||||
| DC | 250 V | - | |||
| GB 14048.2 (Icu/Ics) | AC | 415 V | 70/70 | ||
| 400 V | 75/75 | ||||
| 380 V | 75/75 | ||||
| 230 V | 100/100 | ||||
| DC | 250 V | - | |||
| NK (Icu/Ics) | AC | 450 V | - | ||
| 240 V | - | ||||
| DC | 250 V | - | |||
| Parts included as standard (Surface type) | Circuit Breakers, Mounting screw M4 × 0.7 × 55 (3-position 2 pcs., 4-position 4 pcs.) Insulation barrier (3-position 4 pcs., 4-position 6 pcs.) | ||||

Internal equipment of NF125-HEV
(*) SLT is included from the standard. A control power supply (100 to 240 V AC/DC) is required.
Current reduction curve of NF125-HEV
*Please refer to the catalog for any information not listed above.
| Part Number |
|---|
| NF63-HV 3P 10A |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS |
|---|---|---|---|---|---|
MYR 575.18 | 1 Piece(s) | 9 Day(s) or more | 6 |
Loading...
| Ampere frame | 50AF | Rated block capacity AC 200 V(kA) | 25 | Rated block capacity AC 400 V(kA) | 10 |
|---|---|---|---|---|---|
| Rated Braking Capacity at Rated Voltage of VDC 250(kA) | 7.5 | Number of Poles | 3 | Rated Current(A) | 10 |
| Mounting Method | DIN/Screw retention | Connection Method | Surface type | Representative Standard | PSE / CE / CCC |
| Dimension height(mm) | 130 | Dimension width(mm) | 75 | Dimension depth(mm) | 90 |
| Format | High Performance Products |

MITSUBISHI
Standard Price : MYR 736.91-
Days to Ship : 9 Day(s) or more





How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy