(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Mitsubishi low-voltage breaker contributing to building the future of electrical equipment.
Mitsubishi No-Fuse Breakers and Earth Leakage Circuit Breakers, meeting the needs of the market for over half a century.
Including the new WS-V series equipped with the latest breaker technology, various product ranges are available that address the needs of both the power incoming panel / distribution board market and machinery market.
Part Number
Configured Part Number is shown.
NF32-SVF 3P 20A
| Circuit Breakers Part Number | Circuit Breakers Model NF32-SVF | Circuit Breakers Model NF63-SVF | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Rated Current In Standard Ambient Temperature 40°C A | 3 5 10 15 20 30 | 32 | (3) (5) (10) 15 20 30 40 50 | 60 | (63) | ||||||||
| Number of Positions | 2 | 3 | 2 | 3 | 2 | 3 | 2 | 3 | 2 | 3 | |||
| Rated Insulation Voltage Ui V | 440 | 440 | 440 | 440 | 440 | ||||||||
| Rated Short-Circuit Breaking Capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | - | - | - | - | |||||
| 500 V | - | - | - | - | - | ||||||||
| 440 V | 2.5/2.5 | 2.5/2.5 | 7.5/6 | 7.5/6 | 7.5/6 | ||||||||
| 415 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||||
| 400 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||||
| 380 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||||
| 230 V | 7.5/7.5 | 7.5/7.5 | 15/15 | 15/15 | 15/15 | ||||||||
| DC (*1) | 250 V | - | - | - | - | - | |||||||
| 125 V | 10/10 | 10/10 | 10/10 | 10/10 | 10/10 | ||||||||
| GB 14048.2 (lcu/lcs) | AC | 415 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||
| 400 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||||
| 380 V | 5/5 | 5/5 | 10/8 | 10/8 | 10/8 | ||||||||
| 230 V | 7.5/7.5 | 7.5/7.5 | 15/15 | 15/15 | 15/15 | ||||||||
| DC (*1) | 250 V | - | - | - | - | - | |||||||
| 125 V | 10/10 | 10/10 | 10/10 | 10/10 | 10/10 | ||||||||
| Standard Included Parts (Surface Type) | IEC 35-mm Circuit Breakers Rail Mounting Clip (*2) Insulation Barriers (2 Positions 2 Plates, 3 Positions 4 Plates) | ||||||||||||
*(1) For 3-position Circuit Breakers, use 2 positions.
(2) Only compatible with NF63-SVF 60A and 63A.
Note (1) Mounting screws must be prepared by the customer (recommended size: M4 × 0.7 × 65 [2 pieces])
| Circuit Breakers Part Number | Circuit Breakers Model NF125-SVF | ||||||
|---|---|---|---|---|---|---|---|
| Rated Current In Standard Ambient Temperature for Circuit Breakers 40°C A | 15 20 30 40 50 60 75 100 | 125 | |||||
| Number of Positions | 2 | 3 | 2 | 3 | |||
| Rated Insulation Voltage Ui V | 600 | 600 | |||||
| Rated Short-Circuit Breaking Capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | - | ||
| 500 V | 10/10 | 10/10 | |||||
| 440 V | 20/20 | 20/20 | |||||
| 415 V | 25/25 | 25/25 | |||||
| 400 V | 25/25 | 25/25 | |||||
| 380 V | 25/25 | 25/25 | |||||
| 230 V | 50/50 | 50/50 | |||||
| DC (*1) | 250 V | - | - | ||||
| 125 V | 15/15 | 15/15 | |||||
| GB 14048.2 (lcu/lcs) | AC | 415 V | 25/25 | 25/25 | |||
| 400 V | 25/25 | 25/25 | |||||
| 380 V | 25/25 | 25/25 | |||||
| 230 V | 50/50 | 50/50 | |||||
| DC (*1) | 250 V | - | - | ||||
| 125 V | 15/15 | 15/15 | |||||
| Standard Included Parts (Surface Type) | IEC 35-mm Circuit Breakers Rail Mounting Clip Insulation Barriers (2 Positions 1 Piece, 3 Positions 2 Pieces) M4 × 0.7 × 55 Mounting Screws (2 Pieces) | ||||||
*(1) For 3-position Circuit Breakers, use 2 positions.

Circuit Breakers Model NF32-SVF・NF63-SVF
Surface Type
Note (1) Direct cable connection is not possible.
(2) Motor breakers only have 3 positions.

Circuit Breakers Model NF125-SVF
Surface Type
Note (1) The 2-position product of NF125-SVF is the product where the middle pole of the 3-pole breaker is removed.
| Part Number |
|---|
| NF32-SVF 3P 20A |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Ampere frame | Rated block capacity AC 200 V (kA) | Rated block capacity AC 400 V (kA) | Rated block capacity, voltages except VAC 100/200/400, VDC 250 | Number of Poles | Rated Current (A) | Mounting Method | Representative Standard | Dimension height (mm) | Dimension width (mm) | Dimension depth (mm) | Type | Format | Rated block capacity AC 415 V (kA) | Rated block capacity DC 125 V (kA) | Rated breaking capacity (kA) | Internal included equipment |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
- | 1 Piece(s) | Quote | 30AF | 7.5 | 5 | - | 3 | 20 | DIN/Screw retention | PSE / CE / TUV / CCC | 100 | 54 | 90 | - | General-Purpose Product | - | - | - | - |
Loading...
| Connection Method | Surface type |
|---|
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy