(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Input expansion board for MELSEC-F Series.
[Features]
· Can expand input by 4 points and output by 2 points.
· Expansion board that can be built into an FX3S and FX3G sequencer.
· The power is supplied from the base unit.
Part Number
Configured Part Number is shown.

FX3G-4EX-BD external appearance
Overview/input: 4 points
Approved standards: CE (EMC), KC

FX3G-4EX-BD outline drawing
Unit: mm

Input circuit configuration drawing of FX3G-4EX-BD (sink input)
*1. Service power supply of sequencer main body can be used.

Input circuit configuration drawing of FX3G-4EX-BD (source input)

FX3G-2EYT-BD external appearance
Overview/output: 2 points
Approved standards: CE (EMC), KC

FX3G-2EYT-BD outline drawing
Unit: mm

Output circuit configuration drawing of FX3G-2EYT-BD (sink)

Output circuit configuration drawing of FX3G-2EYT-BD (source)
FX3G-4EX-BD
| Compatible Sequencers | FX3S (V1.10 or later), FX3G (V2.20 or later) | |
|---|---|---|
| Power Supply Specification | ||
| Current Consumption | 5 V DC | Supplied from the sequencer. |
| 24 V DC | Supply power from the external power supply at max. 25 mA. | |
| Input Specification | ||
| Number Of Input Points | 4 points | |
| Input Connection Format | European Terminal Block | |
| Input Format | Sink/Source | |
| Input Signal Voltage | 24 V DC +20%, - 15% | |
| Input Impedance | 4.3 kΩ | |
| Input Signal Current | 5 mA / 24 V DC | |
| Input ON Sensing Current | 3.5 mA or more | |
| Input OFF Sensing Current | 1.5 mA or less | |
| Input Response Time | Approx. 10 ms | |
| Input Signal Format | Sink Input | Non-voltage Contact NPN Open Collector Transistor |
| Source Input | Non-voltage Contact PNP Open Collector Transistor | |
| Input Circuit Insulation | Photocoupler Insulation | |
| Input Operation Indicator | LED turns ON when photocoupler is operated. | |
FX3G-2EYT-BD
| Compatible Sequencers | FX3S (V1.10 or later), FX3G (V2.20 or later) | |
|---|---|---|
| Output Specification | ||
| Number Of Outputs | 2 points | |
| Output Connection Format | European Terminal Block | |
| Output Type / Format | Transistor (sink/source) | |
| External Power Supply | 5 to 30 V DC | |
| Maximum Load | Resistant Load | 0.5 A/point |
| Inductive Load | 12 W / 24 V DC | |
| Leakage Current When Open | 0.1 mA / 30 V DC | |
| ON Voltage | 1.5 V or less | |
| Response Time | OFF→ON | 0.2 ms or less |
| ON→OFF | 0.2 ms or less | |
| Circuit Insulation | Photocoupler Insulation | |
| Output Operation Indicator | LED turns ON when photocoupler is operated. | |
FX3G-4EX-BD
| Ambient Temperature | 0 to 55°C - When Operating, -25 to 75°C - When Saving | ||
|---|---|---|---|
| Relative Humidity | 5 to 95% RH (no condensation) - when operating | ||
| Vibration Resistance | When Mounting To DIN Rail | Frequency: 10 To 57 Hz | Single amplitude: 0.035 mm 10 times in each direction of X, Y and Z (total 80 minutes each) Judgment criteria are based on IEC61131-2. |
| Frequency: 57 To 150 Hz | Acceleration: 4.9 m/s2 10 times in each direction of X, Y and Z (total 80 minutes each) Judgment criteria are based on IEC61131-2. | ||
| When Mounting Directly | Frequency: 10 To 57 Hz | Single amplitude: 0.075 mm 10 times in each direction of X, Y and Z (total 80 minutes each) Judgment criteria are based on IEC61131-2. | |
| Frequency: 57 To 150 Hz | Acceleration: 9.8 m/s2 10 times in each direction of X, Y and Z (total 80 minutes each) Judgment criteria are based on IEC61131-2. | ||
| Impact Resistance | 147 m/s2, for a duration of 11 ms, 3 times in each direction of X, Y and Z with a half-sine pulse. Judgment criteria are based on IEC61131-2. | ||
| Noise Resistance | Judged using a noise simulator with a noise voltage of 1,000 Vp-p, noise width of 1 μs, rise time of 1 ns, and frequency of 30 to 100 Hz. | ||
| Withstand Voltage | Between the input terminal of expansion output board and the earth terminal of base unit: 500 V AC for 1 minute | ||
| Insulation Resistance | Between the input terminal of expansion output board and the earth terminal of base unit: 5 MΩ or more at 500 V DC on an insulation resistance meter | ||
| Operating Atmosphere | There shall be no corrosion gas or flammable gas and not much conductive dust. | ||
| Altitude Of Use | 2,000 m or lower Cannot be used in environments pressurized higher than the atmospheric pressure. Doing so may cause failures. | ||
FX3G-2EYT-BD
| Ambient Temperature | 0 to 55°C - When Operating, -25 to 75°C - When Saving | ||
|---|---|---|---|
| Relative Humidity | 5 to 95% RH (no condensation) - when operating | ||
| Vibration Resistance | When Mounting To DIN Rail | Frequency: 10 To 57 Hz | Single amplitude: 0.035 mm 10 times in each direction of X, Y and Z (total 80 minutes each) Judgment criteria are based on IEC61131-2. |
| Frequency: 57 To 150 Hz | Acceleration: 4.9 m/s2 10 times in each direction of X, Y and Z (total 80 minutes each) Judgment criteria are based on IEC61131-2. | ||
| When Mounting Directly | Frequency: 10 To 57 Hz | Single amplitude: 0.075 mm 10 times in each direction of X, Y and Z (total 80 minutes each) Judgment criteria are based on IEC61131-2. | |
| Frequency: 57 To 150 Hz | Acceleration: 9.8 m/s2 10 times in each direction of X, Y and Z (total 80 minutes each) Judgment criteria are based on IEC61131-2. | ||
| Impact Resistance | 147 m/s2, for a duration of 11 ms, 3 times in each direction of X, Y and Z with a half-sine pulse. Judgment criteria are based on IEC61131-2. | ||
| Noise Resistance | Judged using a noise simulator with a noise voltage of 1,000 Vp-p, noise width of 1 μs, rise time of 1 ns, and frequency of 30 to 100 Hz. | ||
| Withstand Voltage | Between the output terminal of expansion output board and the earth terminal of base unit: 500 V AC for 1 minute | ||
| Insulation Resistance | Between the output terminal of expansion output board and the earth terminal of base unit: 5 MΩ or more at 500 V DC on an insulation resistance meter | ||
| Operating Atmosphere | There shall be no corrosion gas or flammable gas and not much conductive dust. | ||
| Altitude Of Use | 2,000 m or lower Cannot be used in environments pressurized higher than the atmospheric pressure. Doing so may cause failures. | ||
| Part Number |
|---|
| FX3G-2EYT-BD |
| FX3G-4EX-BD |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Number Of Inputs | Rated Input Voltage (V) | Number of Outputs | Output Format | Features | Number of Inputs (Point) | Number of Outputs (Point) | Type of Unit |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
MYR 246.67 MYR 197.34 | 1 Piece(s) | 65 Day(s) | NA | Not available | 2 | Other | Transistor output (sync / source) | NA | 2 | Output | ||
MYR 285.00 MYR 228.00 | 1 Piece(s) | 65 Day(s) | 4 | DC24V | NA | - | - | 4 | NA | Input |
Loading...
| Representative Standard | CE | Applicable sequencer | FX3G / FX3S |
|---|
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy