(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Safety relay unit G9SA
[Features]
· Small size, with an abundant series.
· 45 mm width, with an abundant variety of 3-pole. 5-pole, 3-pole + off delay 2-pole, 2 hand controllers.
· We also offer 17.5 mm width 3-pole, off delay 3-pole expansion units.
· Expansion units can be connected with a single action.
· Off delay types can be set at 15 different time levels.
· Certified ENISO13849-1 (PLe/Safety Category 4).
· Can be DIN rail mounted or screw mounted.
Part Number
Configured Part Number is shown.
G9SA-301 AC/DC24
| Main Contact | Auxiliary Contact | Number of Input Channels | Rated Voltage | Format |
|---|---|---|---|---|
| 3 a | 1 b | 1 ch and 2 ch shared | 24 V AC/DC | Model G9SA-301 |
| 100 to 240 V AC | ||||
| 5 a | 24 V AC/DC | Model G9SA-501 | ||
| 100 to 240 V AC |
Emergency stop unit of Industrial Relays
| Main Contact | OFF Delay Contact | Auxiliary Contact | Number of Input Channels | OFF Delay Time | Rated Voltage | Format |
|---|---|---|---|---|---|---|
| 3 a | 2 a | 1 b | 1 ch and 2 ch shared | 7.5 secs | 24 V AC/DC | Model G9SA-321-T075 |
| 15 secs | 24 V AC/DC | Model G9SA-321-T15 | ||||
| 30 secs | 24 V AC/DC | Model G9SA-321-T30 |
Emergency stop unit with OFF delay of Industrial Relays
The OFF delay time is variable in 15 steps. The following times can be set:
T075: 0.5/1/1.5/2/2.5/3/3.5/4/4.5/5/5.5/6/6.5/7/7.5 secs
T15: 1/2/3/4/5/6/7/8/9/10/11/12/13/14/15 secs
T30: 2/4/6/8/10/12/14/16/18/20/22/24/26/28/30 secs
| Main Contact | Auxiliary Contact | Number of Input Channels | Reset Mode | Input Type | Rated Voltage | Format |
|---|---|---|---|---|---|---|
| 2 a | None | 2 ch | Auto | Inverse | 24 V AC/DC | Model G9SB-2002-A |
| 1 ch, 2 ch | Positive Common | Model G9SB-200-B | ||||
| 2 ch | Manual | Inverse | Model G9SB-2002-C | |||
| 1 ch, 2 ch | Positive Common | Model G9SB-200-D | ||||
| 3 a | 1 b | No (Power supply directly OFF) | Auto | -- | 24 V DC | Model G9SB-3010 |
| 2 ch | Inverse | 24 V AC/DC | Model G9SB-3012-A | |||
| 1 ch, 2 ch | Positive Common | Model G9SB-301-B | ||||
| 2 ch | Manual | Inverse | Model G9SB-3012-C | |||
| 1 ch, 2 ch | Positive Common | Model G9SB-301-D |
| Format | Model G9SA-301 | Model G9SA-501 | Model G9SA-321-T□ |
|---|---|---|---|
| Power Supply Voltage | 24 V AC/DC: 24 V AC, 50/60 Hz / 24 V DC, 100 to 240 V AC: 100 to 240 V AC, 50/60 Hz | ||
| Allowable Voltage Fluctuation Range | Power supply voltage -15% +10% | ||
| Power Consumption | 24 V AC/DC: 1.8 VA/1.7 W max. 100 to 240 V AC: 9 VA max. | 24 V AC/DC: 2.8 VA/2.6 W max. 100 to 240 V AC: 11 VA max. | 24 V AC/DC: 3.5 VA/3.3 W max. 100 to 240 V AC: 12.5 VA max. |
Power supply: G9SA type
| Format | Model G9SB-200□-□ | Model G9SB-3010 | Model G9SB-301□-□ |
|---|---|---|---|
| Power Supply Voltage | 24 V AC/DC: 24 V AC, 50/60 Hz / 24 DC, 24 V DC: 24 V DC | ||
| Allowable Voltage Fluctuation Range | Power supply voltage -15% +10% | ||
| Power Consumption | 1.6 VA / 1.4 W max. | 1.7 W max. | 2.0 VA / 1.7 W max. |
Power supply: G9SB type
| Format | Model G9SA-301/321-T□ | Model G9SA-501 |
|---|---|---|
| Input Current | 40 mA max. | 60 mA max. |
Input: G9SA type
| Format | Model G9SB-200□-□ | Model G9SA-3010 | Model G9SB-301□-□ |
|---|---|---|---|
| Input Current | 25 mA max. | 60 mA max. | 30 mA max. |
Input: G9SB type
| Format | Model G9SA-301/501/321-T□ |
|---|---|
| Load | Resistive Load |
| Rated Load | 250 V AC 5 A, 30 V DC 5 A |
| Rated Carry Current | 5 A |
Switch: G9SA type
| Format | Model G9SB-200□-□, Model G9SB-3010, Model G9SB-301□-□ |
|---|---|
| Load | Resistive Load |
| Rated Load | 250 V AC 5 A, 30 V DC 5 A |
| Rated Carry Current | 5 A |
Switch: G9SB type
| Format | Model G9SA-301 | Model G9SA-501/321-T□ | |
|---|---|---|---|
| Contact Resistance | 100 mΩ | ||
| Operating Time | 30 ms max. | ||
| Response Time | 10 ms max. | ||
| Insulation Resistance | 100 MΩ min., 500 V DC ohmmeter | ||
| Dielectric Strength | Between Different Outputs | 2,500 V AC 50/60 Hz 1 min | |
| Between Input and Output | |||
| Between Power Supply and Output | |||
| Between Power Supply and Input (100 to 240 V AC only) | |||
| Vibration Resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | ||
| Shock Resistance | Durability | 300 m/s2 | |
| Malfunction | 100 m/s2 | ||
| Durability | Mechanical | 5,000,000 operations min. (at approx. 7,200 operations/hr) | |
| Electrical | 100,000 operations min. (at 1,800 operations/hr under rated load) | ||
| Failure Rate (P Level) (Reference Value) | 5 V DC 1 mA | ||
| Ambient Operating Temperature | -25 to +55°C (assuming no icing or condensation) | ||
| Ambient Operating Humidity | 35 to 85% RH | ||
| Terminal Tightening Torque | 0.98 N·m | ||
| Weight | Approx. 210 g | Approx. 270 g | |
| Format | Model G9SB-200□-□ | Model G9SB-3010 | Model G9SB-301□-□ | |
|---|---|---|---|---|
| Contact Resistance | 100 mΩ | |||
| Operating Time | 30 ms max. | |||
| Response Time | 10 ms max. | |||
| Insulation Resistance | 100 MΩ min., 500 V DC ohmmeter | |||
| Dielectric Strength | Between Different Outputs | 2,500 V AC 50/60 Hz 1 min | ||
| Between Input and Output | ||||
| Between Power Supply and Output | ||||
| Vibration Resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | |||
| Shock Resistance | Durability | 300 m/s2 | ||
| Malfunction | 100 m/s2 | |||
| Durability | Mechanical | 5,000,000 operations min. (at approx. 7,200 operations/hr) | ||
| Electrical | 100,000 operations min. (at 1,800 operations/hr under rated load) | |||
| Failure Rate (P Level) (Reference Value) | 5 V DC 1 mA | |||
| Ambient Operating Temperature | -25 to +55°C (assuming no icing or condensation) | |||
| Ambient Operating Humidity | 35 to 85% RH | |||
| Terminal Tightening Torque | 0.5 N·m | |||
| Weight | Approx. 115 g | Approx. 135 g | Approx. 120 g | |
Units: mm

Model G9SA-301
Model G9SA-501
Model G9SA-321-T□ full view

Dimensional outline drawings of Industrial Relays
Units: mm

Model G9SB-200□-□
Model G9SB-3010 full view

Dimensional outline drawings of Industrial Relays
Units: mm

Model G9SB-301□-□ full view

Dimensional outline drawings of Industrial Relays
| Part Number |
|---|
| G9SA-301 AC/DC24 |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Contact Configuration | Latch Function | Terminal Shape | Coil Rated Voltage (AC) (V) | Representative Standard | Dimension Height (mm) | Dimension Width (mm) | Dimension Depth (mm) | Classification | Off Delay Time (Second) | Rated Voltage (V) | Reset Mode | Input Type | Specification | 入力構成 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
MYR 882.00 | 1 Piece(s) | 5 Day(s) or more | [Other] 3a1b | NA | Screw Fastening | 24 | CE / UL / TUV / CCC / CSA | 76 | 45 | 111 | Emergency Stop Unit | - | AC/DC24 | - | - | - | 1ch、2ch |
Loading...
| Application | Safety relay | Contact Rated Current (Minimum Value for AC and DC) (A)(A) | 5 | Coil Rated Voltage (DC)(V) | 24 |
|---|
Please check the type/dimensions/specifications of the part G9SA-301 AC/DC24 in the Safety/Relay Unit G9SA series.
| Part Number |
|---|
| G9SA-301 AC100-240 |
| G9SA-321-T075 AC/DC24 |
| G9SA-321-T075-P DC24 |
| G9SA-321-T15 AC/DC24 |
| G9SA-321-T30 AC/DC24 |
| G9SA-501 AC/DC24 |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Contact Configuration | Latch Function | Terminal Shape | Coil Rated Voltage (AC) (V) | Representative Standard | Dimension Height (mm) | Dimension Width (mm) | Dimension Depth (mm) | Classification | Off Delay Time (Second) | Rated Voltage (V) | Reset Mode | Input Type | Specification | 入力構成 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
MYR 1,121.83 | 1 Piece(s) | 5 Day(s) or more | [Other] 3a1b | NA | Screw Fastening | 100~240 | CE / UL / TUV / CCC / CSA | 76 | 45 | 111 | Emergency Stop Unit | - | AC100-240 | - | - | - | 1ch、2ch | ||
MYR 1,594.81 | 1 Piece(s) | 2 Day(s) | [Other] 3a2a1b | NA | Screw Fastening | 24 | CE / UL / TUV / CCC / CSA | 76 | 45 | 111 | Emergency Stop Unit - With OFF Delay | 7.5 | AC/DC24 | - | - | - | 1ch、2ch | ||
MYR 1,603.00 | 1 Piece(s) | 9 Day(s) or more | [Other] 3a2a1b | - | - | - | UL / TUV / CCC / CSA | 76 | 45 | 111 | Emergency Stop Unit - With OFF Delay | 7.5 | DC24 | - | Negative Common (NPN) | - | 1ch、2ch | ||
MYR 1,594.81 | 1 Piece(s) | 5 Day(s) or more | [Other] 3a2a1b | NA | Screw Fastening | 24 | CE / UL / TUV / CCC / CSA | 76 | 45 | 111 | Emergency Stop Unit - With OFF Delay | 15 | AC/DC24 | - | - | - | 1ch、2ch | ||
MYR 1,594.81 | 1 Piece(s) | 5 Day(s) or more | [Other] 3a2a1b | NA | Screw Fastening | 24 | CE / UL / TUV / CCC / CSA | 76 | 45 | 111 | Emergency Stop Unit - With OFF Delay | 30 | AC/DC24 | - | - | - | 1ch、2ch | ||
MYR 1,440.10 | 1 Piece(s) | 5 Day(s) or more | [Other] 5a1b | NA | Screw Fastening | 24 | CE / UL / TUV / CCC / CSA | 76 | 45 | 111 | Emergency Stop Unit | - | AC/DC24 | - | - | - | 1ch、2ch |






How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy