(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Ultra-small timer for use in sequence control incorporating a dedicated IC.
[Features]
· Highly accurate with a repeat error of ±1% (including first time value).
· Recovery time including recovery during operation is 100 ms or less.
· Time is easily set using the large dial that works with either straight-slot or Phillips-head screwdrivers.
· Semi-multi power supply voltages.
· Standard product complies with UL and CSA standards.
· EN61812-1 compatible, conforms to the CE mark.
[Applications]
· Many facilities require timer functions, and this can be used anywhere on the line.
Part Number
Configured Part Number is shown.
H3Y-2 DC24 60S

External appearance of H3Y
| Maximum scale time | Time Setting Range |
|---|---|
| 0.5 s | 0.04 s to 0.5 s |
| 1s | 0.1 s to 1.0 s |
| 5 s | 0.2 s to 5.0 s |
| 10 s | 0.5s to 10 s |
| 30 s | 1.0 s to 30 s |
| 60 s | 2.0 s to 60 s |
| 120 s | 5.0 s to 120 s |
| 3 min | 0.1 min to 3 min |
| 5 min | 0.2 min to 5 min |
| 10 min | 0.5 min to 10 min |
| 30 min | 1.0 min to 30 min |
| 60 min | 2.0 min to 60 min |
| 3 h | 0.1 h to 3 h |
| Model number | Series H3Y-2 (-0) | Series H3Y-4 (-0) | |
|---|---|---|---|
| Power supply voltage *6 | ・ 100 to 120 V AC, 50/60 Hz, 200 to 230 V AC, 50/60 Hz ・ 24 V AC, 50/60 Hz *1 ・DC12V ・DC24V ・DC48V ・DC100 to 110 V ・DC125V *2, *3 | ||
| Allowable voltage fluctuation range | 85 to 110% of power supply voltage (However, 90 to 110% of power supply voltage only for 12 V DC specifications) *4 | ||
| Power consumption | AC100 to 120 V | 1.5 VA (at 120 V AC) | |
| AC200 to 230 V | 1.8 VA (at 230 V AC) | ||
| AC24V | 1.5 VA (at 24 V AC) | ||
| DC12V | 0.9 W (at 12 V DC) | ||
| DC24V | 0.9 W (at 24 V DC) | ||
| DC48V | 1.0 W (at 48 V DC) | ||
| DC100 to 110 V | 1.3 W (at 110 V DC) | ||
| DC125V | 1.3 W (at 125 V DC) | ||
| Reset voltage | 10% or more of power supply voltage *5 | ||
| Control output | 250 V AC 5 A, resistant load (cosø = 1) Minimum compatible load 5 V DC 1 mA (P level, reference value) Contact Materials: Ag | 250 V AC 3 A, resistant load (cosø = 1) Minimum compatible load 1 V DC 1 mA (P level, reference value) Contact Materials: Au clad + Ag alloy | |
| Operating Ambient Temperature | -10 to +50℃ (However, do not freeze) | ||
| Storage temperature | -25 to +65℃ (However, do not freeze) | ||
| Operating ambient humidity | 35 to 85% | ||
*1. The inverter output should not be used as a power supply.
*2. Single-phase, full-wave-rectified power supplies can be used.
*3. Only the H3Y-2 and H3Y-2-0 types include 12 V DC models.
* 4. When using continuously at an operating ambient temperature of 50°C, 90 to 110% of the power supply voltage (95 to 110% for 12 V DC) should be used.
* 5. For reliable reset, 100 to 120 V AC should be set to 10 V AC, 200 to 230 V AC should be set to 20 V AC, and 100 to 110 V DC should be set to 10 V DC or less.
*6. A diode to prevent reverse voltages is provided only on models with a DC power supply voltage.
| Model number | Series H3Y-2 (-0) | Series H3Y-4 (-0) | |
|---|---|---|---|
| Accuracy of operating time | ±1% or less (at maximum scale time) *1 | ||
| Setting error | ±10% ±50 ms max. (at maximum scale time) | ||
| Reset time | 0.1 s max. (including halfway reset) | ||
| Influence of voltage | ±2% or less (at maximum scale time) *1 | ||
| Influence of temperature | ±2% or less (at maximum scale time) *1 | ||
| Insulation resistance | 100 MΩ or more (Measured at 500 V DC insulation resistance tester) | ||
| Withstand voltage | 2,000 V AC, 50/60 Hz for 1 min (Between current-carrying terminals and exposed non-current-carrying metal parts, except for the terminal thread section) 2,000 V AC, 50/60 Hz for 1 min (Between operating power supply circuit and control output) 2,000 V AC, 50/60 Hz for 1 min (Between different pole contacts; 2-pole model) 1,500 V AC 50/60 Hz 1 min (Between different pole contacts; 4-pole model) 1,000 V AC 50/60 Hz 1 min (Between non-continuous contacts) | ||
| Impulse voltage | Between power supply terminals: 3 kV, 1 kV for 12 V DC, 24 V DC, 48 V DC Between exposed non-current-carrying metal parts: 4.5 kV, 1.5 kV for 12 V DC, 24 V DC, 48 V DC | ||
| Noise immunity | Square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) ±1.5 kV | ||
| Static immunity | Malfunction: 4 kV, Destruction: 8 kV | ||
| Vibration | Destruction | 10 to 55 Hz, 0.75-mm single amplitude for 1 h each in 3 directions | |
| Malfunction | 10 to 55 Hz, 0.5-mm single amplitude for 10 min each in 3 directions | ||
| Impact | Destruction | 1,000 m/s^2 for 3 times each in 6 directions *2 | |
| Malfunction | 100 m/s^2 for 3 times each in 6 directions | ||
| Lifespan | Mechanical | 10,000,000 operations min. (under no load at 1,800 operations/h) | |
| Electrical | 2-pole: 500,000 operations min. (250 V AC 5 A, resistant load at 1,800 operations/h) (At normal temperature) 4-pole: 200,000 operations min. (250 V AC 3 A, resistant load at 1,800 operations/h) (At normal temperature) | ||
| Protective structure | IP40 | ||
| Weight | Approx. 50 g | ||
*1. ±10 ms is added to the above value for the 0.5 s range model.
*2. The destructive impact resistance test was performed on the timer.
| Part Number |
|---|
| H3Y-2 DC24 60S |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Time Specifications (s) | Power Supply Voltage | Rated Power Supply Voltage (V) | Contact Configuration | Terminal shape | Terminal Arrangement | Body Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
MYR 171.34 | 1 Piece(s) | 2 Day(s) | 2.0s to 60s | Dedicated to DC | DC24 | Time Limit 2c | Plug-in terminal | Top: output terminal, Bottom: power supply terminal | Beige |
Loading...
| Type | Timer | Display Method | Analog | Mounting Method | Surface mounting |
|---|---|---|---|---|---|
| Output Method | Relay | Representative Standard | CE / UL / CCC / CSA | Dimension Vertical(mm) | 28 |
| Dimension Width(mm) | 21.5 | Dimension Depth(mm) | 56.6 | Time Ranges = N | 1 range |
Please check the type/dimensions/specifications of the part H3Y-2 DC24 60S in the Solid State/Timer H3Y series.
| Part Number |
|---|
| H3Y-2 AC100-120 120S |
| H3Y-2 AC100-120 1S |
| H3Y-2 AC100-120 30M |
| H3Y-2 DC48 10S |
| H3Y-2 DC48 30S |
| H3Y-2 DC48 5S |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Time Specifications (s) | Power Supply Voltage | Rated Power Supply Voltage (V) | Contact Configuration | Terminal shape | Terminal Arrangement | Body Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
MYR 190.72 | 1 Piece(s) | 5 Day(s) or more | 5.0s to 120s | AC-dedicated | AC100 to 120 | Time Limit 2c | Plug-in terminal | Top: output terminal, Bottom: power supply terminal | Beige | ||
MYR 198.45 | 1 Piece(s) | 5 Day(s) or more | 0.1s to 1.0s | AC-dedicated | AC100 to 120 | Time Limit 2c | Plug-in terminal | Top: output terminal, Bottom: power supply terminal | Beige | ||
MYR 190.72 | 1 Piece(s) | 5 Day(s) or more | 1.0m to 30m | AC-dedicated | AC100 to 120 | Time Limit 2c | Plug-in terminal | Top: output terminal, Bottom: power supply terminal | Beige | ||
MYR 195.91 | 1 Piece(s) | 5 Day(s) or more | 0.5s to 10s | Dedicated to DC | DC48 | Time Limit 2c | Plug-in terminal | - | - | ||
MYR 163.61 | 1 Piece(s) | 5 Day(s) or more | 1.0s to 30s | Dedicated to DC | DC48 | Time Limit 2c | Plug-in terminal | Top: output terminal, Bottom: power supply terminal | Beige | ||
MYR 163.61 | 1 Piece(s) | 5 Day(s) or more | 0.2s to 5.0s | Dedicated to DC | DC48 | Time Limit 2c | Plug-in terminal | Top: output terminal, Bottom: power supply terminal | Beige |

OMRON
Standard Price : MYR 6.86-
Days to Ship : 2 Day(s) or more




OMRON
Standard Price : MYR 2.08-
Days to Ship : 2 Day(s) or more




OMRON
Standard Price : MYR 309.04-
Days to Ship : 2 Day(s) or more



OMRON
Standard Price : MYR 20.54-
Days to Ship : 2 Day(s) or more
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy