(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
WS series NV-F type earth leakage breaker supporting higher harmonic surge (standard product).
[Features]
· Earth leakage breaker with earth leakage detection characteristics, unlikely to have unnecessary earth leakage tripping in response to higher harmonics or surges.
· Also applicable to inverter load because a higher harmonics and surge compatible IC is built in.
· Can provide IEC rail mounting as standard.
· Can mount on front surface, without tightening nuts from the back.
· Terminal structure allows back surface wiring.
[Applications]
· Earth leakage breaker supporting higher harmonic surge.
Part Number
Configured Part Number is shown.
Earth Leakage Breakers, Unified breaker vertical dimension for miniature relay socket vertical dimension of 72 mm.
Also applicable to inverter load because a higher harmonics and surge compatible IC is built in.
Can provide IEC rail mounting as standard.
Can mount on front surface, without tightening nuts from the back.
Terminal structure allows back surface wiring.

| Frame A | 30 | 50 | |||||
|---|---|---|---|---|---|---|---|
| Type Name | NV30-FAU | NV50-FAU | |||||
| Phase Wire Model | ø 1, 2 W | 3 ø 3 W 1 ø 2 W | ø 1, 2 W | 3 ø 3 W 1 ø 2 W | |||
| Rated Current In A Standard Ambient Temperature 40°C | 5 10 15 20 30 | 5 10 15 20 30 40 50 | |||||
| Number Of Contacts | 2 | 3 | 2 | 3 | |||
| High Speed Type | Rated Sensitivity Current mA | 30 | |||||
| Pickup Current UL 1053 | I△n × 75% | ||||||
| Maximum Operating Time s | 0.04 (at 5I△n) (Note 3) | ||||||
| Rated Short Circuit Breaking Capacity kA | UL 1077 CSA C22.2 No. 235 | Rated Voltage | AC V | 240 | 240 | ||
| AC | 240 V | 2.5 (Note 1) | 2.5 (Note 1) | ||||
| IEC 60947-2 EN 60947-2 GB 14048.2 (Icu/Ics) | Rated Operating Voltage Ue V | AC | 230 | 230 | |||
| AC | 230 V | 2.5/1 (Note 2) | 2.5/1 (Note 2) | ||||
| JIS C 8201-2-2 Ann.1 Ann.2 (Icu/Ics) (Note 4) | Rated Operating Voltage Ue V | AC | 100-200 | 100-200 | |||
| AC | 200 V | 2.5/1 (Note 2) | 2.5/1 (Note 2) | ||||
| 100 V | 2.5/1 (Note 2) | 2.5/1 (Note 2) | |||||
| Rated Impulse Withstand Voltage Uimp (kV) | 2.5 | ||||||
| Current Type | AC | AC | |||||
| Isolation Compliant | - | - | |||||
| Reverse Connections | - | - | |||||
| Selectability Type (Usage Category) | A | ||||||
| Degree Of Contamination | 2 | ||||||
| EMC Environmental Conditions (Environment A Or Environment B) | A | ||||||
| External Dimensions (mm) | a | 40 | 60 | 40 | 60 | ||
| b | 72 | 72 | |||||
| c | 57 | 57 | |||||
| ca | 73.5 | 73.5 | |||||
| Connection Method | Front Surface Type | For Crimp Terminals | Possible | Possible | |||
| Simple Back Surface Type | For Crimp Terminals | Possible | Possible | ||||
| IEC 35 mm Rail Mounting | Possible | Possible | |||||
| Electrical Appliance And Material Safety Law | Compliant | Compliant | |||||
| Overcurrent Tripping Method | Thermal | Thermal | |||||
| Trip Button | - | - | |||||
| CE Mark | TÜV certification | TÜV certification | |||||
| CCC Certification | acquired | acquired | |||||
Note 1: The rated breaking capacity is 1.5 kA for parts with 5 A rated current.
Note 2: The rated breaking capacity is 1.5/1 kA for parts with 5 A rated current.
Note 3: 0.1 for UL1053.
Note 4 NV30-FA and NV50-FA only display JIS C 8201-2-2 Ann.2.
Earth Leakage Breakers, Rated breaking capacity is 5 kA (200 V AC or 240 V AC) (dedicated product for AC circuits)
Screw mounting and IEC 35 mm rail mounting are available as standard.
Motor circuit protection characteristics are also standard. Motor protection rated current is set for NF50-FHU and NV50-FHU types.

| Frame A | 50 | ||||
|---|---|---|---|---|---|
| Type Name | NV50-FHU | ||||
| Phase Wire Model | ø 1, 2 W | ⌀3 3 W, ⌀1 2 W, ⌀1 3 W | |||
| Rated Current In A Standard Ambient Temperature 40°C | 5 10 15 20 30 40 50 | ||||
| Rated Current For Motor Protection (Note 1) | - | 1.4 2.5 4 6.3 7.1 16 25 32 45 | |||
| Number Of Contacts | 2 | 3 | |||
| High Speed Type | Rated Sensitivity Current mA | 30, 50, 100 | |||
| Pickup Current UL 1053 | I△n × 75% | ||||
| Maximum Operating Time s | 0.04 (at 5I△n) (Note 3) | ||||
| Rated Short Circuit Breaking Capacity kA | UL 1077 CSA C22.2 No. 235 | Rated Voltage | AC V | 240 | |
| AC | 240 V | 5 | |||
| IEC 60947-2 EN 60947-2 (Icu/Ics) | Rated Operating Voltage Ue V | AC | 230 | ||
| AC | 230 V | 5/2 | |||
| GB 14048.2 (Icu/Ics) | Rated Operating Voltage Ue V | AC | 240 | ||
| AC | 240 V | 5/2 | |||
| JIS C 8201-2-2 Ann.1 Ann.2 (Icu/Ics) | Rated Operating Voltage Ue V | AC | 100-200 | ||
| AC | 200 V | 5/2 | |||
| 100 V | 5/2 | ||||
| Rated Impulse Withstand Voltage Uimp (kV) | 4 | ||||
| Current Type | AC | ||||
| Isolation Compliant | - | ||||
| Reverse Connections | - | ||||
| Selectability Type (Usage Category) | A | ||||
| Degree Of Contamination | 2 | ||||
| EMC Environmental Conditions (Environment A Or Environment B) | A | ||||
| External Dimensions (mm) | a | 50 | 75 | ||
| b | 96 | ||||
| c | 60 | ||||
| ca | 76 | ||||
| Connection Method | Front Surface Type | For Crimp Terminals | Possible | ||
| Mounting Method | IEC 35 mm Rail | Possible | |||
| Mounting Screw (Note 2) | Possible | ||||
| Electrical Appliance And Material Safety Law | Compliant | ||||
| Overcurrent Tripping Method | Completely electromagnetic | ||||
| Trip Button | - | ||||
| CE Mark | TÜV certification | ||||
| CCC Certification | acquired | ||||
Note 1: For rated current for motor protection, only current sensitivities of 30 mA or 50 mA can be fabricated.
Note 2: The customer must provide the mounting screws.
Note 3: 0.1 for UL 1053.
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS | Ampere frame AF | Rated block capacity AC 100 V (kA) | Rated block capacity AC 200 V (kA) | Number of Poles | Rated Current (A) | rate sensitivity current (mA) | Dimension height (mm) | Dimension width (mm) | Dimension depth (mm) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
MYR 392.35 | 1 Piece(s) | 31 Day(s) | 6 | 30AF | 1.5 | 1.5 | 2 | 5 | 30 | 72 | 40 | 73.5 | ||
- | 1 Piece(s) | Quote | 6 | 30AF | 2.5 | 2.5 | 2 | 20 | 30 | 72 | 40 | 73.5 | ||
MYR 572.09 | 1 Piece(s) | Quote | - | 30AF | 1.5 | 1.5 | 3 | 5 | 30 | 72 | 60 | 73.5 | ||
MYR 594.60 | 1 Piece(s) | Quote | 6 | 30AF | 2.5 | 2.5 | 3 | 10 | 30 | 72 | 60 | 73.5 | ||
MYR 713.61 | 1 Piece(s) | 14 Day(s) or more | - | 30AF | 2.5 | 2.5 | 3 | 30 | 30 | 72 | 60 | 73.5 | ||
- | 1 Piece(s) | Quote | 6 | 50AF | 2.5 | 2.5 | 3 | 50 | 30 | 72 | 60 | 73.5 | ||
- | 1 Piece(s) | Quote | - | 50AF | 5 | 5 | 2 | 40 | 100 | 96 | 50 | 76 |
Loading...
| Rated Operating Voltage(V) | AC100 to 200 | Mounting Method | DIN/Screw retention | Representative Standard | PSE / CE / TUV / CCC |
|---|---|---|---|---|---|
| Connection Method | Surface form | Type | For control panel | Features | High harmonic surge support type |
| Phase display | NA |

MITSUBISHI
Days to Ship : 27 Day(s) or more


MITSUBISHI
Days to Ship : Quote

MITSUBISHI
Days to Ship : 16 Day(s) or more




MITSUBISHI
Days to Ship : 9 Day(s) or more

MITSUBISHI
Days to Ship : 8 Day(s) or more


MITSUBISHI
Days to Ship : Quote
![EBS series (distribution-panel type leak breaker) [EBS32FB]](http://my.misumi-ec.com/linked/material/el/LSI1/PHOTO/LSI1_82.jpg?$product_recommend_b$)
LSIS
Standard Price : MYR 150.58-
Days to Ship : 1 Day(s) or more
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy