(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
WS-V series NF-C type no-fuse breaker (economy product).
[Features]
· Small, high performance, and economical no-fuse breaker.
· Smallest breaker in the industry.
· Connection method: front surface type, back surface type, embedded type, inserted type.
[Applications]
· No-fuse breaker, economy product.
Part Number
Configured Part Number is shown.
| Type Name Circuit Breakers | NF63-CV Circuit Breakers | ||||
|---|---|---|---|---|---|
| Rated current In Standard ambient temperature 40°C (45°C for ships) A | 60 | ||||
| Number of contacts | 2 | 3 | |||
| Rated Insulation Voltage Ui V | 600 | ||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-1 Ann. 1 JIS C 8201-2-1 Ann. 2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | |
| 500 V | 2.5/2.5 | ||||
| 440 V | 2.5/2.5 | ||||
| 415 V | 2.5/2.5 | ||||
| 400 V | 5/5 | ||||
| 380 V | 5/5 | ||||
| 230 V | 7.5/7.5 | ||||
| DC | 250 V (Note 1) | 2.5/2.5 | |||
| GB 14048.2 (Icu/Ics) | AC | 415 V | 2.5/2.5 | ||
| 400 V | 5/5 | ||||
| 380 V | 5/5 | ||||
| 230 V | 7.5/7.5 | ||||
| DC | 250 V | 2.5/2.5 | |||
| NK (Icu/Ics) | AC | 450 V | 2.5/2.5 | ||
| 240 V | 7.5/7.5 | ||||
| DC | 250 V | 2.5/2.5 | - | ||
Note 1: For 3-contact products, use two contacts.




| Type Name Circuit Breakers | NF125-CV Circuit Breakers | ||||||
|---|---|---|---|---|---|---|---|
| Rated current In Standard ambient temperature 40°C (45°C for ships) A | (50) 60 75 100 | 125 | |||||
| Number of contacts | 2 | 3 | 2 | 3 | |||
| Rated Insulation Voltage Ui V | 600 | 600 | |||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-1Ann. 1 JIS C 8201-2-1Ann. 2 IEC 60947-2 EN 60947-2 (Icu/Ics) | AC | 690 V | - | - | ||
| 500 V | 7.5/4 | 7.5/4 | |||||
| 440 V | 10/5 | 10/5 | |||||
| 415 V | 10/5 | 10/5 | |||||
| 400 V | 10/5 | 10/5 | |||||
| 380 V | 10/5 | 10/5 | |||||
| 230 V | 30/15 | 30/15 | |||||
| DC | 250 V (Note 1) | 7.5/4 | 7.5/4 | ||||
| GB 14048.2 (Icu/Ics) | AC | 415 V | 10/5 | 10/5 | |||
| 400 V | 10/5 | 10/5 | |||||
| 380 V | 10/5 | 10/5 | |||||
| 230 V | 30/15 | 30/15 | |||||
| DC | 250 V | 7.5/4 | 7.5/4 | ||||
| NK (Icu/Ics) | AC | 450 V | 10/5 | 10/5 | |||
| 240 V | 30/15 | 30/15 | |||||
| DC | 250 V | 7.5/4 | - | 7.5/4 | - | ||
Note 1: For 3-contact products, use two contacts.



Note: NF125-CV for 2 and 3 contacts only, and motor breaker for 3 contacts only.

| Part Number |
|---|
| NF250-CV 3P 200A FP |
| NF250-CV 3P 225A |
| NF250-CV 3P 225A FP |
| NF250-CV 3P 250A |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS | Ampere frame | Rated block capacity AC 200 V (kA) | Rated Current (A) | Connection Method |
|---|---|---|---|---|---|---|---|---|---|
- | 1 Piece(s) | Quote | 6 | [200AF to 399AF] 225AF | - | 200 | Embedded Type | ||
- | 1 Piece(s) | Quote | 6 | [200AF to 399AF] 225AF | 36 | 225 | Surface type | ||
MYR 1,392.51 | 1 Piece(s) | 9 Day(s) or more | 6 | [200AF to 399AF] 225AF | - | 225 | Embedded Type | ||
- | 1 Piece(s) | Quote | - | [200AF to 399AF] 250AF | - | 250 | Surface type |
Loading...
| Rated block capacity AC 400 V(kA) | 25 | Rated Braking Capacity at Rated Voltage of VDC 250(kA) | 15 | Number of Poles | 3 |
|---|---|---|---|---|---|
| Mounting Method | Fasten With Screws | Representative Standard | CE / TUV / CCC | Dimension height(mm) | 165 |
| Dimension width(mm) | 105 | Dimension depth(mm) | 92 | Format | Economical Products |







MITSUBISHI
Standard Price : MYR 736.91-
Days to Ship : 9 Day(s) or more
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy