(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
CC-Link/LT analog input unit.
[Features]
· 4 channels.
· Input: -10 to 10 V DC, 0 to 20 mA DC.
· Output (resolution): 0 to 4,000, -4,000 to 4,000.
· Conversion speed: 200 µs / 4 channels.
· Number of occupied stations: 4 stations in 16‑point mode
[Applications]
· Network communication.
Part Number
Configured Part Number is shown.
CL2AD4-B

CL2AD4-B external appearance

CL2AD4-B dimensional outline drawing (unit: mm)
| Analog Input Points | 4 points (4 channels) | ||
|---|---|---|---|
| Analog Input | Voltage | -10 to +10 V DC (input resistance: 11 MΩ) | |
| Current | 0 to 20 mA DC (input resistance: 250 Ω) | ||
| Digital Output | -4,096 to +4,095 | ||
| Input/Output Characteristics, Resolution | Input Range | Digital Output Value (Maximum Resolution) | |
| Voltage Input | 0 To 10 V | 0 to 4,000 (2.5 mV) | |
| 0 To 5 V | 0 to 4,000 (1.25 mV) | ||
| 1 To 5 V | 0 to 4,000 (1.0 mV) | ||
| -10 To 10 V | -4,000 to 4,000 (2.5 mV) | ||
| Current Input | 0 To 20 mA | 0 to 4,000 (5 μA) | |
| 4 To 20 mA | 0 to 4,000 (4 μA) | ||
| Precision (Precision With Respect To Maximum Digital Output Value) | Ambient Temperature: 25±5°C | ±0.2% | |
| Ambient Temperature: 0 To 55°C | ±0.4% | ||
| Temperature Coefficient | ±80 ppm/°C (0.0080%/°C) | ||
| A/D Conversion Speed | 200 µs / 4 channels | ||
| Absolute Maximum Input | Voltage | ±15 V | |
| Current | ±30 mA | ||
| Isolation Method | Between communication system and all analog inputs at once: photocoupler insulation, transformer insulation Between power supply system and all analog inputs at once: photocoupler insulation, transformer insulation Between communication system and power supply system: photocoupler insulation, transformer insulation Between channels: non-insulation | ||
| Dielectric Strength | Between communication system and all analog inputs at once, between power supply system and all analog inputs at once, between communication system and power supply system: 500 V AC for 1 minute | ||
| Insulation Resistance | Between communication system and all analog inputs at once, between power supply system and all analog inputs at once, between communication system and power supply system: 10 MΩ or more at 500 V DC | ||
| Protection Grade | IP2X | ||
| Number Of Occupied Stations | 4 stations in 16-point mode | ||
| Unit Power Supply | Voltage | 24 V DC (20.4 to 28.8 V DC, Ripple Ratio within 5%) | |
| Current | 70 mA | ||
| Current At Startup | 570 mA | ||
| External Wiring Connection Method | 14-point Direct Attachment Terminal Block (M3 Screw) | ||
| Mass | 0.15 kg | ||
| Ambient Operating Temperature | 0 to 55℃ | ||
|---|---|---|---|
| Ambient Storage Temperature | -25 to 75℃ | ||
| Ambient Operating Humidity | 5 to 95% RH, assuming no condensation | ||
| Ambient Storage Humidity | 5 to 95% RH, assuming no condensation | ||
| Vibration Resistance | JIS B 3502, IEC 61131-2 compliant | Under Intermittent Vibration | Frequency: 5 to 8.4 Hz, Amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, Acceleration: 9.8 m/s2 Sweeps: 10 sweeps in each direction of X, Y and Z |
| Under Continuous Vibration | Frequency: 5 to 8.4 Hz, Amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Acceleration: 4.9 m/s2 | ||
| Impact Resistance | Conforms to JIS B 3502, IEC 61131-2 (147 m/s2, 3 sweeps in 3 directions of X, Y and Z) | ||
| Operating Atmosphere | No corrosive gas | ||
| Operating Altitude | 0 to 2,000 m | ||
| Installation Location | Inside the control panel | ||
| Overvoltage Category | II or lower | ||
| Pollution Degree | 2 or less | ||
| Part Number |
|---|
| CL2AD4-B |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS |
|---|---|---|---|---|---|
- | 1 Piece(s) | Quote | 6 |
Loading...
| Type | Input | Input Type | Voltage / Current | Number of Input Channels | 4 |
|---|---|---|---|---|---|
| A/D Conversion Speed (Conversion Time) | 100 to Less Than 500 μS | Terminal shape | Terminal Block | Representative Standard | CE / UL |
| Voltage input range | DC-10V to 10V | Current input range | DC 0–20 mA |
Please check the type/dimensions/specifications of the part CL2AD4-B in the CC-Link Analog Input Unit Terminal Block Type series.

MITSUBISHI
Standard Price : MYR 1,796.67-
Days to Ship : 4 Day(s) or more

CK_KINZOKU
Standard Price : MYR 127.95-
Days to Ship : 13 Day(s) or more

DOGYUSANGYO
Standard Price : MYR 820.93
Days to Ship : 8 Day(s)
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy