(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
WS-V Series NV-C Type Earth Leakage Circuit Breaker (Economy Model) F Style.
[Features]
· Has a small size that is the smallest class in the industry, while maintaining conventional breaking performance.
[Applications]
· Earth leakage circuit breaker, F style.
Part Number
Configured Part Number is shown.
| Type Name of Earth Leakage Breakers | NV63-CVF | ||||
|---|---|---|---|---|---|
| Rated Current In Standard ambient temperature 40°C | A | 60 | |||
| Number of contacts | 2 | 3 | |||
| Phase wire model | ø 1, 2 W | 1 ø 2 W, 3 ø 3 W, 1 ø 3 W | |||
| Rated operating voltage Ue V | AC | 100- 240 | 100- 440 | ||
| High-speed type | Rated sensitivity current mA | 30 | 30 100 200 500 | ||
| Maximum operating time s | at I △n | 0.1 | |||
| at 5I △n | 0.04 | ||||
| Time-delay type | Rated sensitivity current mA | - | |||
| Maximum operating time s | - | ||||
| Inertia dead time s or more | - | ||||
| Electrical leakage display method | Display window | ||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-2 Ann. 1 JIS C 8201-2-2 Ann. 2 IEC 60947-2 2nd. ed. (Icu/Ics) | AC | 440 V | - | 2.5/2.5 |
| 415 V | - | 5/5 | |||
| 400 V | - | 5/5 | |||
| 230 V | 7.5/7.5 | ||||
| 200 V | 7.5/7.5 | ||||
| 100 V | 7.5/7.5 | ||||

Note: Wires cannot be connected directly. Motor breaker is 3-contact only.
| Type Name | NV125-CVF | ||||
|---|---|---|---|---|---|
| Rated current In (Note 2) Standard ambient temperature 40°C | A | 60 75 100 | 125 | ||
| Number of contacts | 3 | 3 | |||
| Phase wire model | ⌀3 3 W, ⌀1 3 W, ⌀1 2 W | ⌀3 3 W, ⌀1 3 W, ⌀1 2 W | |||
| Rated operating voltage Ue V (Note 1) | AC | 100-440 | 100-440 | ||
| High-speed type | Rated sensitivity current mA | 30 100/200/500 switch | 30 100/200/500 switch | ||
| Maximum operating time s | at I △n | 0.1 | 0.1 | ||
| at 5I △n | 0.04 | 0.04 | |||
| Time-delay type | Rated sensitivity current mA | (100/200/500 switch) | (100/200/500 switch) | ||
| Maximum operating time s | (0.45/1.0/2.0 switch) | (0.45/1.0/2.0 switch) | |||
| Inertia dead time s or more | (0.1/0.5/1.0) | (0.1/0.5/1.0) | |||
| Electrical leakage display method | Mechanical button | ||||
| Rated short circuit breaking capacity kA | JIS C 8201-2-2 Ann. 1 JIS C 8201-2-2 Ann. 2 IEC 60947-2 2nd (Icu/Ics) | AC | 440 V | 10/5 | 10/5 |
| 415 V | 10/5 | 10/5 | |||
| 400 V | 10/5 | 10/5 | |||
| 230 V | 30/15 | 30/15 | |||
| 200 V | 30/15 | 30/15 | |||
| 100 V | 30/15 | 30/15 | |||
Note 1: The time-delay type rated operating voltage is 200-440 V.
Note 2: The time-delay type is fabricated at 20 A or higher.

| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS | Ampere frame AF | Rated block capacity AC 100 V (kA) | Rated block capacity AC 200 V (kA) | Rated block capacity AC 400 V (kA) | Number of Poles | Rated Current (A) | rate sensitivity current (mA) | Representative Standard | Dimension height (mm) | Dimension width (mm) | Rated block capacity, voltages except VAC 100/200/400, VDC 250 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
- | 1 Piece(s) | 13 Day(s) or more | 6 | 60AF | 7.5 | 7.5 | - | 2 | 60 | 30 | PSE | 100 | 36 | Available | ||
- | 1 Piece(s) | Quote | 6 | 60AF | 7.5 | 7.5 | - | 2 | 60 | 30 | PSE | 100 | 36 | - | ||
- | 1 Piece(s) | Quote | 6 | 60AF | 7.5 | 7.5 | 5 | 3 | 60 | 30 | PSE | 100 | 54 | Available | ||
- | 1 Piece(s) | Quote | 6 | 60AF | 7.5 | 7.5 | 5 | 3 | 60 | 30 | PSE | 100 | 54 | - | ||
- | 1 Piece(s) | Quote | 6 | 60AF | 7.5 | 7.5 | 5 | 3 | 60 | 100 | PSE | 100 | 54 | - | ||
- | 1 Piece(s) | Quote | 6 | [100AF to 199AF] 125AF | 30 | 30 | 10 | 3 | 60 | 100· 200· 500 switch | PSE | 130 | 75 | Available | ||
- | 1 Piece(s) | Quote | 6 | 60AF | 30 | 30 | 10 | 3 | 60 | 30 | PSE | 130 | 75 | - | ||
- | 1 Piece(s) | Quote | 6 | [100AF to 199AF] 125AF | 30 | 30 | 10 | 3 | 75 | 100· 200· 500 switch | PSE | 130 | 75 | Available | ||
- | 1 Piece(s) | Quote | 6 | [100AF to 199AF] 125AF | 30 | 30 | 10 | 3 | 75 | 30 | PSE | 130 | 75 | - | ||
- | 1 Piece(s) | Quote | 6 | [100AF to 199AF] 125AF | 30 | 30 | 10 | 3 | 100 | 100· 200· 500 switch | PSE | 130 | 75 | Available | ||
- | 1 Piece(s) | Quote | 10 | [100AF to 199AF] 100AF | 30 | 30 | 10 | 3 | 100 | 30 | PSE | 130 | 75 | - | ||
- | 1 Piece(s) | Quote | 6 | [100AF to 199AF] 125AF | 30 | 30 | 10 | 3 | 125 | 100· 200· 500 switch | - | 130 | 75 | Available | ||
- | 1 Piece(s) | Quote | 6 | [100AF to 199AF] 125AF | 30 | 30 | 10 | 3 | 125 | 30 | - | 130 | 75 | - |
Loading...
| Rated Operating Voltage(V) | AC100 to 440 | Mounting Method | DIN/Screw retention | Dimension depth(mm) | 90 |
|---|---|---|---|---|---|
| Connection Method | Surface form | Type | Economical Products | Specifications | High Harmonics/Surge Compatible Table |


MITSUBISHI
Days to Ship : Quote


MITSUBISHI
Days to Ship : 9 Day(s) or more

MITSUBISHI
Days to Ship : 14 Day(s) or more

MITSUBISHI
Days to Ship : 8 Day(s) or more


How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy