Mitsubishi electromagnetic switch.
[Features]
· Uses power semiconductor element to enable long life when using as a high frequency switch.
[Applications]
· Optimal as a non-contact AC semiconductor contactor.
Part Number
Configured Part Number is shown.
US-N8SSTE
| 3-Contact Type | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Type Name | Standard | 3-Contact 2-Element Type | US-N5SS | US-N8SS | US-N20 | US-N30 | US-N40 | US-N50 | US-N70NS | US-N80NS | US-NH70NS | US-NH80NS |
| 3-Contact 3-Element Type | US-N5SSTE | US-N8SSTE | US-N20TE | US-N30TE | US-N40TE | US-N50TE | US-N70NSTE | US-N80NSTE | US-NH70NSTE | US-NH80NSTE | ||
| With CAN Terminal | 3-Contact 2-Element Type | - | - | US-N20CX | US-N30CX | US-N40CX | US-N50CX | - | - | - | - | |
| 3-Contact 3-Element Type | - | - | US-N20TECX | US-N30TECX | US-N40TECX | US-N50TECX | - | - | - | - | ||
| IEC 35 mm Rail Mounting | 3-Contact 2-Element Type | (Note 1) | (Note 1) | US-N20RM | - | - | - | - | - | - | - | |
| 3-Contact 3-Element Type | (Note 1) | (Note 1) | US-N20TERM | - | - | - | - | - | - | - | ||
| Rating | Rated Operating Current (-10 To 40°C) (Note 2) | JEM (AC-1 Class) | 5 A | 8 A | 20 A | 30 A | 40 A | 50 A | 70 A | 80 A | 70 A | 80 A |
| IEC (AC-51 Class) | 5 A | 8 A | 20 A | 30 A | 40 A | 50 A [45 A]Note 3 | 70 A | 80 A | 65 A | 75 A | ||
| Applied Heater Capacity (-10 To 40°C) | 1 Ø 200 V (Note 4) | 1 kW | 1.6 kW | 4 kW | 6 kW | 8 kW | 10 kW [9 kW]Note 3 | 14 kW | 16 kW | 14 kW | 16 kW | |
| 3 Ø 200 V | 1.7 kW | 2.7 kW | 6.9 kW | 10.3 kW | 13.8 kW | 17.3 kW [15.5 kW]Note 3 | 24.2 kW | 27.7 kW | 24.2 kW | 27.7 kW | ||
| 1 Ø 400 V (Note 4) | - | - | 8 kW | 12 kW | 16 kW | 20 kW [18 kW]Note 3 | - | - | 28 kW | 32 kW | ||
| 3 Ø 400 V | - | - | 13.8 kW | 20.7 kW | 27.7 kW | 34.6 kW [31.1 kW]Note 3 | - | - | 48.5 kW | 55.4 kW | ||
| Maximum Applicable Motor Capacity (Maximum Operating Current (Note 5)) | 3 Ø 200 V | 0.4 kW (3.2 A) | 0.4 kW (3.2 A) | 2.2 kW (11.1 A) | 3.7 kW (17.4 A) | 5.5 kW (26 A) | 5.5 kW (26 A) | 11 kW (48 A) | 11 kW (48 A) | 11 kW (48 A) | 11 kW (48 A) | |
| 3 Ø 400 V | - | - | 3.7 kW (8.7 A) | 7.5 kW (17.4 A) | 11 kW (26 A) | 11 kW (26 A) | - | - | 22 kW (48 A) | 22 kW (48 A) | ||
| Minimum Load Current | 150 mA | 300 mA | ||||||||||
| Main Circuit Specifications | Main Circuit Control Method | Batch control | ||||||||||
| Rated Operating Voltage | 100 to 240 V AC 50/60 Hz | 100 to 480 V AC 50/60 Hz | 100 to 240 V AC 50/60 Hz | 200 to 480 V AC 50/60 Hz | ||||||||
| Operating Voltage Range | 85 to 110% of rated operating voltage | |||||||||||
| Rated Insulation Voltage | 250 V AC | 500 V AC | 250 V AC | 500 V AC | ||||||||
| Voltage Drop Upon Closing | 1.5 V/phase | |||||||||||
| Leakage Current When Closing | 15 mA or less (240 V AC 60 Hz) | 30 mA or less (480 V AC 60 Hz) | 30 mA or less (240 V AC 60 Hz) | 30 mA or less (480 V AC 60 Hz) | ||||||||
| Surge On Current (60 Hz, Half-Wave 1 Cycle Wave Height Value) | 160 A | 800 A | 1,300 A | 1,800 A | ||||||||
| Tolerance Ⅰ2t(A2S) | 106 | 2,600 | 7,000 | 13,500 | ||||||||
| Trigger Method | Zero voltage trigger method | |||||||||||
| Closing And Breaking Current Capacity | 32 A | 50 A | 111 A | 174 A | 260 A | 480 A | ||||||
| Operating Circuit Specifications | Rated Operating Voltage | 12 to 24 V DC (voltage ripple rate 10% or less) | ||||||||||
| Operating Voltage Fluctuation Range | 85 to 110% of rated operating voltage | |||||||||||
| Operation Circuit Maximum Applied Voltage | 26.4 V DC | |||||||||||
| Operation Circuit Voltage Input Current | 20 mA (12 to 24 V DC) | 5 mA (12 to 24 V DC) | 20 mA (12 to 24 V DC) | |||||||||
| Input Impedance | 0.6 to 1.2 kΩ | 2.4 to 4.8 kΩ | 0.6 to 1.2 kΩ | |||||||||
| Operating Voltage | 9 V DC or less | |||||||||||
| Open Circuit Voltage | 3 V DC or more | |||||||||||
| Response Time | Maximum 1 ms + 1/2 cycle | |||||||||||
| Operating Display | Operating display LED indicator lamp (on when applying operating voltage) | |||||||||||
| Cooling Fan Operating Voltage | - | 200 to 240 V AC 50/60 Hz | ||||||||||
| Fan Fault Detection Output | Contact Configuration | - | b-Contact | |||||||||
| Contact Capacity | - | 5 to 24 V DC/100 to 240 V AC 0.1 A | ||||||||||
| Common Specifications | Withstand Voltage | 2 kV | 2.5 kV | 2 kV | 2.5 kV | |||||||
| Insulation Resistance | 100 MΩ | |||||||||||
| Rated Impulse Withstand Voltage (Note 6) | 4 kV | 6 kV | 4 kV | 6 kV | ||||||||
| Ambient Operating Temperature | -10 to 60°C (At 40°C or higher, use reduced current) | |||||||||||
| Relative Temperature | 45 to 85% RH | |||||||||||
| Altitude | 2,000 m or less | |||||||||||
| Vibration Resistance | 10 to 55 Hz 19.6 m/s2 | |||||||||||
| Shock Resistance | 98 m/s2 | |||||||||||

Figure 1
| Part Number |
|---|
| US-N8SSTE |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS | Dimension length (mm) | Dimension width (mm) | Dimension thickness (mm) | Specifications | Motor capacity 400 VAC (kW/A) | Motor Capacity VAC 200 (kW/A) | Number of Elements (Piece) | Rated current used (A) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
- | 1 Piece(s) | Quote | 6 | 76 | 45 | 112 | 3-pole 3-element form | - | 0.4/3.2 | 3 | 8 |
Loading...
| Operating Method | Irreversible type | Coil rated voltage(V) | DC 12–24 | Number of Poles | 3 |
|---|---|---|---|---|---|
| Representative Standard | CE / UL / TUV / CCC / CSA | Equipment Name | Solid state contactor | Finger protection/terminal cover | NA |
Please check the type/dimensions/specifications of the part US-N8SSTE in the Solid State Contactors US-N Series series.
| Part Number |
|---|
| US-N20 |
| US-N20TE |
| US-N30TE |
| US-N40TE |
| US-N50 |
| US-N5SS |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS | Dimension length (mm) | Dimension width (mm) | Dimension thickness (mm) | Specifications | Motor capacity 400 VAC (kW/A) | Motor Capacity VAC 200 (kW/A) | Number of Elements (Piece) | Rated current used (A) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
- | 1 Piece(s) | Quote | 6 | 100 | 90 | 107 | Standard Form | 3.7/8.7 | 2.2/11.1 | 2 | 20 | ||
- | 1 Piece(s) | Quote | 6 | 100 | 90 | 107 | 3-pole 3-element form | 3.7/8.7 | 2.2/11.1 | 3 | 20 | ||
- | 1 Piece(s) | Quote | 6 | 120 | 110 | 135 | 3-pole 3-element form | 7.5/17.4 | 3.7/17.4 | 3 | 30 | ||
- | 1 Piece(s) | Quote | 6 | 120 | 110 | 135 | 3-pole 3-element form | 46352 | 5.5/26 | 3 | 40 | ||
- | 1 Piece(s) | Quote | 6 | 120 | 110 | 135 | Standard Form | 46352 | 5.5/26 | 2 | 50 | ||
- | 1 Piece(s) | Quote | 6 | 76 | 45 | 87 | Standard Form | - | 0.4/3.2 | 2 | 5 |







OMRON
Standard Price : MYR 166.99-
Days to Ship : 2 Day(s) or more
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy