(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.

  • [Announcement] MISUMI Malaysia website new user interface. Clearer navigation, easy product search and more. Explore now! May contact us at (60) 3 7890 6399 for any inquiries.

Solid State Contactors US-N Series (US-N8SSTE)

Solid State Contactors US-N Series US-N8SSTE

Mitsubishi electromagnetic switch.
[Features]
· Uses power semiconductor element to enable long life when using as a high frequency switch.
[Applications]
· Optimal as a non-contact AC semiconductor contactor.

PDF

Part Number

Configured Part Number is shown.

US-N8SSTE

Solid State Contactor US-N Series Features

  • Optimal for motor load in high-frequency switching, such as on a transport line, etc. Can also be used with a heater load.
  • The load current switching operation is performed by a semiconductor switching element, and as there are no mechanical parts, a long life with highly frequent switching can be achieved.
  • As there are no mechanical movable parts or abrading parts, no abrasion dust or contact consumption dust is created, resulting in clean, noiseless and comfortable use.
  • Operation indicator lamp on the front surface allows users to see the operating voltage input status at a glance.

Solid State Contactor US-N Series Specifications

3-Contact Type
Type
Name
Standard3-Contact 2-Element TypeUS-N5SSUS-N8SSUS-N20US-N30US-N40US-N50US-N70NSUS-N80NSUS-NH70NSUS-NH80NS
3-Contact 3-Element TypeUS-N5SSTEUS-N8SSTEUS-N20TEUS-N30TEUS-N40TEUS-N50TEUS-N70NSTEUS-N80NSTEUS-NH70NSTEUS-NH80NSTE
With CAN Terminal3-Contact 2-Element Type--US-N20CXUS-N30CXUS-N40CXUS-N50CX----
3-Contact 3-Element Type--US-N20TECXUS-N30TECXUS-N40TECXUS-N50TECX----
IEC
35 mm Rail Mounting
3-Contact 2-Element Type(Note 1)(Note 1)US-N20RM-------
3-Contact 3-Element Type(Note 1)(Note 1)US-N20TERM-------
Rating
Rated Operating Current
(-10 To 40°C) (Note 2)
JEM (AC-1 Class)5 A8 A20 A30 A40 A50 A70 A80 A70 A80 A
IEC (AC-51 Class)5 A8 A20 A30 A40 A50 A [45 A]Note 370 A80 A65 A75 A
Applied Heater Capacity
(-10 To 40°C)
1 Ø 200 V (Note 4)1 kW1.6 kW4 kW6 kW8 kW10 kW [9 kW]Note 314 kW16 kW14 kW16 kW
3 Ø 200 V1.7 kW2.7 kW6.9 kW10.3 kW13.8 kW17.3 kW [15.5 kW]Note 324.2 kW27.7 kW24.2 kW27.7 kW
1 Ø 400 V (Note 4)--8 kW12 kW16 kW20 kW [18 kW]Note 3--28 kW32 kW
3 Ø 400 V--13.8 kW20.7 kW27.7 kW34.6 kW [31.1 kW]Note 3--48.5 kW55.4 kW
Maximum Applicable Motor Capacity
(Maximum Operating Current (Note 5))
3 Ø 200 V0.4 kW (3.2 A)0.4 kW (3.2 A)2.2 kW (11.1 A)3.7 kW (17.4 A)5.5 kW (26 A)5.5 kW (26 A)11 kW (48 A)11 kW (48 A)11 kW (48 A)11 kW (48 A)
3 Ø 400 V--3.7 kW (8.7 A)7.5 kW (17.4 A)11 kW (26 A)11 kW (26 A)--22 kW (48 A)22 kW (48 A)
Minimum Load Current150 mA300 mA
Main
Circuit
Specifications

Main Circuit Control MethodBatch control
Rated Operating Voltage100 to 240 V AC 50/60 Hz100 to 480 V AC 50/60 Hz100 to 240 V AC 50/60 Hz200 to 480 V AC 50/60 Hz
Operating Voltage Range85 to 110% of rated operating voltage
Rated Insulation Voltage250 V AC500 V AC250 V AC500 V AC
Voltage Drop Upon Closing1.5 V/phase
Leakage Current When Closing15 mA or less (240 V AC 60 Hz)30 mA or less (480 V AC 60 Hz)30 mA or less (240 V AC 60 Hz)30 mA or less (480 V AC 60 Hz)
Surge On Current
(60 Hz, Half-Wave 1 Cycle Wave Height Value)
160 A800 A1,300 A1,800 A
Tolerance Ⅰ2t(A2S)1062,6007,00013,500
Trigger MethodZero voltage trigger method
Closing And Breaking Current Capacity32 A50 A111 A174 A260 A480 A
Operating
Circuit
Specifications


Rated Operating Voltage12 to 24 V DC (voltage ripple rate 10% or less)
Operating Voltage Fluctuation Range85 to 110% of rated operating voltage
Operation Circuit Maximum Applied Voltage26.4 V DC
Operation Circuit Voltage Input Current20 mA (12 to 24 V DC)5 mA (12 to 24 V DC)20 mA (12 to 24 V DC)
Input Impedance0.6 to 1.2 kΩ2.4 to 4.8 kΩ0.6 to 1.2 kΩ
Operating Voltage9 V DC or less
Open Circuit Voltage3 V DC or more
Response TimeMaximum 1 ms + 1/2 cycle
Operating DisplayOperating display LED indicator lamp (on when applying operating voltage)
Cooling Fan Operating Voltage-200 to 240 V AC 50/60 Hz
Fan Fault
Detection Output
Contact Configuration-b-Contact
Contact Capacity-5 to 24 V DC/100 to 240 V AC 0.1 A
Common
Specifications

Withstand Voltage2 kV2.5 kV2 kV2.5 kV
Insulation Resistance100 MΩ
Rated Impulse Withstand Voltage (Note 6)4 kV6 kV4 kV6 kV
Ambient Operating Temperature-10 to 60°C (At 40°C or higher, use reduced current)
Relative Temperature45 to 85% RH
Altitude2,000 m or less
Vibration Resistance10 to 55 Hz 19.6 m/s2
Shock Resistance98 m/s2
Figure 1

Figure 1

  • Note 1: Can be used with standard products.
  • Note 2: If the ambient temperature exceeds 40°C. Multiply the reduction rate shown in Figure 1 by the rated operating current, and use that value.
  • Note 3: Values in [ ] indicate the IEC (AC-51 class) rating for the US-N50TE (CX) type.
  • Note 4: Indicates capacity per single element.
  • Note 5: Indicates capacity that is applicable when selecting based on solid state contactor element capacity.
  • Note 6: Follows IEC60947-1.
Part Number
US-N8SSTE
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRoHSDimension length
(mm)
Dimension width
(mm)
Dimension thickness
(mm)
Specifications Motor capacity 400 VAC
(kW/A)
Motor Capacity VAC 200
(kW/A)
Number of Elements
(Piece)
Rated current used
(A)

-

1 Piece(s) Quote 676451123-pole 3-element form-0.4/3.238

Loading...

  1. 1
 

Basic Information

Operating Method Irreversible type Coil rated voltage(V) DC 12–24 Number of Poles 3
Representative Standard CE / UL / TUV / CCC / CSA Equipment Name Solid state contactor Finger protection/terminal cover NA

Please check the type/dimensions/specifications of the part US-N8SSTE in the Solid State Contactors US-N Series series.

Products like this...

Part Number
US-N20
US-N20TE
US-N30TE
US-N40TE
US-N50
US-N5SS
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRoHSDimension length
(mm)
Dimension width
(mm)
Dimension thickness
(mm)
Specifications Motor capacity 400 VAC
(kW/A)
Motor Capacity VAC 200
(kW/A)
Number of Elements
(Piece)
Rated current used
(A)

-

1 Piece(s) Quote 610090107Standard Form3.7/8.72.2/11.1220

-

1 Piece(s) Quote 6100901073-pole 3-element form3.7/8.72.2/11.1320

-

1 Piece(s) Quote 61201101353-pole 3-element form7.5/17.43.7/17.4330

-

1 Piece(s) Quote 61201101353-pole 3-element form463525.5/26340

-

1 Piece(s) Quote 6120110135Standard Form463525.5/26250

-

1 Piece(s) Quote 6764587Standard Form-0.4/3.225

Additional Products in this Category

Customers Who Viewed This Item Also Viewed

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(60) 3 7890 6399
9:00am - 6:00pm (Monday - Friday)
9:00am - 1:00pm (Saturday)