(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Mitsubishi electromagnetic switch.
[Features]
· Simple current setting, manual check possible.
[Applications]
· Optimal for the overload and locking protection of a standard motor.
Part Number
Configured Part Number is shown.
| Type | Thermal relay | ||
|---|---|---|---|
| Product | Overload protection type thermal relay | ||
| Series | TH-N | ||
| Type Name | TH-N220HZ | ||
| Number Of Elements | 2-element | ||
| Settling Current Adjustment Range | 65 to 220 A | ||
| Heater Nominal [A] Note 1 | (1) | 82 (65 to 100) 105 (85 to 125) 125 (100 to 150) 150 (120 to 180) | |
| (2) | 180 (140 to 220) | ||
| Power Consumption [VA/Element] Minimum/Maximum Settling Time | 1.0/2.3 Note 3 | ||
| Terminal Screw Size | M10 | ||
| Match To Terminal | Wire Size [mm2] | - | |
| Crimp Terminal Size | 22-10 to 150-10 | ||
| Contact Configuration | 1a1b | ||
| Open Thermocurrent lth (A) | 5 | ||
| Rated Operating Current [A] | AC-15 Class (AC Electromagnetic Contactor Coil Switch) a-Contact / b-Contact - Note 2 | 24 V AC | 2 (0.5) / 3 (0.5) |
| 120 V AC | 2 (0.5) / 3 (0.5) | ||
| 240 V AC | 1 (0.5) / 2 (0.5) | ||
| 550 V AC | 0.5 (0.5) / 1 (0.5) | ||
| DC-13 Class (DC Electromagnetic Contactor Coil Switch) a-Contact/b-Contact - Note 2 | 24 V DC | 1 (0.3) | |
| 110 V DC | 0.2 (0.2) | ||
| 220 V DC | 0.1 (0.1) | ||
| Minimum Applied Load Level | 20 V 5 mA | ||
| Terminal Screw Size | M4 | ||
|---|---|---|---|
| Wire Size Matching Terminal | Wire Size [mm2] | ø1.6, 1.25 to 2 | |
| Crimp Terminal Size | 1.25 to 4 to 2-4, 5.5-S4 | ||
| Electromagnetic Contactor Frame To Combine - Note 1 | (1) | N180, N220 | |
| (2) | N220 | ||
| Single-Unit Mounting | Yes | ||
| Terminal Cover | Standard Terminal Cover | N/A | |
| Wiring Streamlining Terminal Function | N/A | ||
| Usage Conditions | Ambient Temperature [°C] | -10 to +40°C (standard is 20°C, maximum temperature in panel 55°C) | |
| Frequency [Hz] | 0 (DC) to 400 | ||
| Additional Functions/Options | No additional functions/options | ||
| Type | Thermal relay | ||
|---|---|---|---|
| Product | Overload protection type thermal relay | ||
| Series | TH-N | ||
| Type Name | TH-N400HZ | ||
| Number Of Elements | 2-element | ||
| Settling Current Adjustment Range | 85 to 400 A | ||
| Heater Nominal [A] Note 1 | (1) | 105 (85 to 125) 125 (100 to 150) 150 (120 to 180) 180 (140 to 220) 250 (200 to 300) | |
| (2) | 330 (260 to 400) Note 3 | ||
| Power Consumption [VA/Element] Minimum/Maximum Settling Time | 1.0/2.3 Note 4 | ||
| Terminal Screw Size | M12 | ||
| Match To Terminal | Wire Size [mm2] | - | |
| Crimp Terminal Size | 22-12 to 200-12 | ||
| Contact Configuration | 1a1b | ||
| Open Thermocurrent lth (A) | 5 | ||
| Rated Operating Current [A] | AC-15 Class (AC Electromagnetic Contactor Coil Switch) a-Contact / b-Contact - Note 2 | 24 V AC | 2 (0.5) / 3 (0.5) |
| 120 V AC | 2 (0.5) / 3 (0.5) | ||
| 240 V AC | 1 (0.5) / 2 (0.5) | ||
| 550 V AC | 0.5 (0.5) / 1 (0.5) | ||
| DC-13 Class (DC Electromagnetic Contactor Coil Switch) a-Contact/b-Contact - Note 2 | 24 V DC | 1 (0.3) | |
| 110 V DC | 0.2 (0.2) | ||
| 220 V DC | 0.1 (0.1) | ||
| Minimum Applied Load Level | 20 V 5 mA | ||
| Terminal Screw Size | M4 | ||
|---|---|---|---|
| Wire Size Matching Terminal | Wire Size [mm2] | ø1.6, 1.25 to 2 | |
| Crimp Terminal Size | 1.25 to 4 to 2-4, 5.5-S4 | ||
| Electromagnetic Contactor Frame To Combine - Note 1 | (1) | N300, N400 | |
| (2) | N400 | ||
| Single-Unit Mounting | Yes | ||
| Terminal Cover | Standard Terminal Cover | N/A | |
| Wiring Streamlining Terminal Function | N/A | ||
| Usage Conditions | Ambient Temperature [°C] | -10 to +40°C (standard is 20°C, maximum temperature in panel 55°C) | |
| Frequency [Hz] | 0 (DC) to 400 | ||
| Additional Functions/Options | No additional functions/options | ||
| Part Number |
|---|
| TH-N220HZ 82A |
| TH-N220HZ 105A |
| TH-N220HZ 125A |
| TH-N220HZ 150A |
| TH-N220HZ 180A |
| TH-N400HZ 250A |
| TH-N400HZ 330A |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS | Motor capacity/nominal thermal nominal size 440 VAC (kW/A) | Motor Capacity / Thermal Nominal Size VAC 220 (kW/A) | Dimension width (mm) | Frame Size | Nominal heater size (A) |
|---|---|---|---|---|---|---|---|---|---|---|
MYR 907.47 | 1 Piece(s) | 9 Day(s) or more | 6 | 45/82 | 22/82 | 104 | N220 | 82 | ||
MYR 907.47 | 1 Piece(s) | 9 Day(s) or more | 6 | 55/105 | 30/105 | 104 | N220 | 105 | ||
MYR 1,196.38 | 1 Piece(s) | 9 Day(s) or more | 6 | 75/125 | 37/125 | 104 | N220 | 125 | ||
MYR 1,196.38 | 1 Piece(s) | 9 Day(s) or more | 6 | 90/150 | 45/150 | 104 | N220 | 150 | ||
MYR 907.47 | 1 Piece(s) | 9 Day(s) or more | 6 | 110/180 | 55/180 | 104 | N220 | 180 | ||
MYR 1,291.14 | 1 Piece(s) | 9 Day(s) or more | 6 | 160/250 | 75/250 | 173 | N400 | 250 | ||
MYR 1,291.14 | 1 Piece(s) | 9 Day(s) or more | 6 | 200/330 | 110/330 | 173 | N400 | 330 |
Loading...
| Number of Poles | 3 | Auxiliary Contact | 1a1b | Dimension length(mm) | 144 |
|---|---|---|---|---|---|
| Dimension thickness(mm) | 166.5 | Specifications | Standard/2 elements | Finger protection/terminal cover | NA |






How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy