A compact type with a built-in detachment device and deterioration indicator
[Features]
· Includes a built-in detachment device. Includes a deterioration indicator.
· The built-in detachment mechanism prevents the SPD from smoking and/or igniting in cases where the ZnO element deteriorates.
· With function for indicating detachment mechanism operation.
· Compact, enables space-saving.
· Combined type between wires and ground protecting from lightning-induced surges.
· Use of multi‐terminal components helped in making the smallest product in the industry. Same dimensions are available for 200V to 500V.
· Safe lightning surge bearing strength.
· Using maximum discharge current 5kA (8 / 20 μs), it is difficult to break even with a large lightning surge.
· A long service life type that stands up to repeated lightning surges of 1000A500 times.
Japanese Only
Part Number
Configured Part Number is shown.
| Part Number |
|---|
| LT-C12G801W |
| LT-C14G801W |
| LT-C32G801W |
| LT-C34G801W |
| LT-C35G102W |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS | Voltage | Maximum Continuous Operational Voltage | Voltage protection level | Direct current discharge starting voltage | Voltage when starting operations | Number of phases, number of wires |
|---|---|---|---|---|---|---|---|---|---|---|---|
MYR 187.73 | 1 Piece(s) | 4 Day(s) or more | 10 | 200V | AC275V | 1.5kV | Between line and ground 800V ± 20% | Line 540V ± 10% | Single-phase 2-line | ||
MYR 235.21 | 1 Piece(s) | 4 Day(s) or more | - | 400V | Line AC480V/ ground 280V | 1.8kV | Between line and ground 800V ± 20% | Line 940V ± 10% | Single-phase 2-line | ||
MYR 187.73 | 1 Piece(s) | 4 Day(s) or more | 10 | 200V | AC275V | 1.5kV | Between line and ground 800V ± 20% | Line 540V ± 10% | Three-phase three-line | ||
MYR 235.21 | 1 Piece(s) | 4 Day(s) or more | - | 400V | Y wire connection AC 480 V/△ wire connection 280V | 1.8kV | Between line and ground 800V ± 20% | Line 940V ± 10% | Three-phase three-line | ||
MYR 262.18 | 1 Piece(s) | 4 Day(s) or more | - | 500V | Y wire connection AC 550 V/△ wire connection 320 V | 2.0kV | Between line and ground 1000 V ± 20% | Line 1100V ± 10% | Three-phase three-line |
Loading...
| Application | Power Supply | Type | Integrated | Mounting Method | Cord direct removal |
|---|---|---|---|---|---|
| Class, category | Class II | Representative Standard | UL / CUL / TUV / CSA | Dimension vertical(mm) | 33.5 |
| Dimension width(mm) | 38 | Dimension depth(mm) | 28 | Nominal Discharge Current (8/20 μs) | 2500A |
| Maximum Discharge Current (8/20 μs) | 5000A |


OTOWA
Standard Price : MYR 760.57-
Days to Ship : 4 Day(s) or more

OTOWA
Standard Price : MYR 297.08-
Days to Ship : 4 Day(s) or more
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy