(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
This air-cooled aftercooler does not require cooling equipment, and maintenance is easy without concerns about water supply cut-off or freezing.
[Features]
· Cools high temperature compressed air from a compressor down to 40°C or less and removes moisture from the air.
· Compact size and light weight.
· Uses minimal floor space.
· Built-in drain separator.
· Dust-protecting filter optional.
Part Number
Configured Part Number is shown.
HAA15-103DFS-T

HAA15 external appearance

HAA7 external appearance

Working Principle
| Model | HAA7 | HAA15 | HAA22 | HAA37 | ||||
|---|---|---|---|---|---|---|---|---|
| Rated conditions | Air flow capacity L/min (ANR)*1 | 1,000 | 2,200 | 3,300 | 5,700 | |||
| Inlet air temperature (°C) | 70 | |||||||
| Inlet air pressure (MPa) | 0.7 | |||||||
| Ambient temperature (°C) | 32 | |||||||
| Outlet air temperature (°C) | 40 | |||||||
| Operating range | Applicable fluid | Compressed Air | ||||||
| Inlet air temperature (°C) | 5 to 100 | |||||||
| Inlet air pressure (MPa) | 0.05 to 1.0 (With auto drain: 0.15 to 1.0) | 0.05 to 0.97 (With auto drain: 0.15 to 0.97) | ||||||
| Ambient temperature (°C) | 2 to 50 | |||||||
| Installation location | Indoors | |||||||
| Electric specifications | Power supply | Single-phase 100 V AC (50/60 Hz) | Single-phase 200 V AC (50/60 Hz) | Single-phase 100 V AC (50/60 Hz) | Three-phase 200 V AC (50/60 Hz) | Three-phase 200 V AC (50/60 Hz) | Three-phase 200 V AC (50/60 Hz) | |
| Power consumption (W) | 50 Hz | 55 | 58 | 55 | 50 | 90 | 204 | |
| 60 Hz | 58 | 65 | 65 | 60 | 130 | 244 | ||
| Current (A) | 50 Hz | 0.8 | 0.43 | 0.8 | 0.4 | 0.4 | 2.0 | |
| 60 Hz | 0.81 | 0.46 | 0.9 | 0.35 | 0.45 | 2.0 | ||
| Proof pressure (MPa) | 1.5 | |||||||
| Cooling fan diameter (mm) | 255 | 300 | 400 | 350 × 2 pcs. | ||||
| Cooler | Aluminum plate tube with fins | |||||||
| Port size for inlet/outlet air | Rp3/4 socket | 1B union | 1 1/2 B union | |||||
| Port size for drain outlet piping (With auto drain) | Rc 3/8 (Rc 3/8) | Rc 1/2 (Rc 3/8) | ||||||
| Weight (kg) | 18 | 24 | 36 | 55 | ||||
| Coating color | Munsell N-8 (white), Munsell 2.5PB5/8.5 (blue) | |||||||
| Applicable compressor (kW)*2 | 7.5 | 15 | 22 | 37 | ||||
| Standard equipment | Thermometer for outlet air temperature (1 pc.) | - | ● | ● | ● | |||
| Accessories*3 | Drain valve (1 pc.) | 3/8B | 1/2B | |||||
| Union (2 pcs.) | - | 1B | 1 1/2 B | |||||
*1: ANR is the value at 20°C, atmospheric pressure and relative humidity 65%.
*2: The applicable compressor is based on the discharge rate and discharge temperature (70°C) of a screw-type compressor.
*3: Accessories should be mounted by the user.
(Unit: mm)

Dimensions: HAA7
(Unit: mm)

HAA15-22 dimensions
(Unit: mm)

HAA37 dimensions
(Unit: mm)
| Model | Piping connection port diameter | A | B | C | D | E | F | G | H | J | K | L | M | N | P | Q | R | S |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| HAA15 | 1B union | 460 | 394 | 33 | 70 | 59 | 485 | 428 | 320 | 150 | 150 | 320 | 70 | 58 | 200 | 480 | 220 | 225 |
| HAA22 | 1 1/2B union | 588 | 484 | 52 | 70 | 60 | 580 | 505 | 333 | 150 | 150 | 400 | 94 | 65 | 200 | 610 | 220 | 238 |
The outlet air temperature can be calculated by the inlet air temperature, ambient temperature and air flow capacity using the following procedure.
(Example) Inlet air temperature: 100°C, Ambient temperature: 20°C, Air flow capacity: 2,000 L/min (ANR), Air pressure:
0.7 MPa, Model: HAA22-14

Correction factor by ambient temperature
| Model | Correction factor line | Air flow (L/min [ANR]) | Inlet air temperature | ||
|---|---|---|---|---|---|
| 50°C | 70°C | 100°C | |||
| HAA7 | (A) | 500 | 34.5 | 35 | 35.5 |
| (B) | 1,000 | 38 | 40 | 42.5 | |
| (C) | 1,500 | 40 | 44 | 47.5 | |
| HAA15 | (A) | 1,000 | 33 | 35.5 | 36 |
| (B) | 2,200 | 36.5 | 40 | 42.5 | |
| (C) | 3,000 | 38 | 42 | 44 | |
| HAA22 | (A) | 2,000 | 34 | 37 | 38.5 |
| (B) | 3,300 | 36 | 40 | 42.5 | |
| (C) | 4,000 | 37 | 41.5 | 45 | |
| HAA37 | (A) | 4,000 | 34 | 38 | 39 |
| (B) | 5,700 | 35 | 40 | 43 | |
| (C) | 7,000 | 36 | 42 | 45 | |
Conditions:
Caution
Caution

If the aftercooler is equipped with an auto drain, the following mounting frame is necessary. Mounting frame (Option: Refer to p. 11 Accessories)
Caution
| Part Number |
|---|
| HAA15-103DFS-T |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Air compressor size (screw type) (KW) | Piping connection port diameter | Power supply voltage (V) | Auto drain | Filter for dust intrusion prevention | Frame | Terminal |
|---|---|---|---|---|---|---|---|---|---|---|---|
MYR 9,194.11 | 1 Piece(s) | 26 Day(s) or more | 15 | 1B | Three-phase 200 | With auto drain | With dust-protecting filter | With mounting frame | With terminal |
Loading...
| Type | After Cooler |
|---|
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy