Fieldbus System (For Output) EX120/121/122 Series compatible with a variety of communication networks.
[Features]
· Output type for solenoid valve.
Part Number
Configured Part Number is shown.
EX122-SCS1

SI Unit model number notation image
| Communication Specifications | Terminating Resistor | Not provided |
|---|---|---|
| Internal Current Consumption (Unit) | 100 mA or less | |
| Environment Resistance | Enclosure | IP20 |
| Operating Temperature Range | 0 to +55°C (valve 8 points ON) 0 to +50℃ (valve 16 points ON) | |
| Operating Humidity Range | 35 to 85% RH (No condensation) | |
| Withstand Voltage | 1,500 V AC for 1 minute between external terminal and housing | |
| Insulation Resistance | 500 V DC, 2 MΩ or more between external terminal and housing | |
| Model | EX12□-SDN1 | EX12□-SDN1-X26 | EX12□-SMJ1 | EX12□-SCS1 EX12□-SCS2 | |
|---|---|---|---|---|---|
| Communication Specifications | Protocol Name | DeviceNetTM | CC-Link | Made by OMRON CompoBus/S | |
| Version*1 | Release 2.0 | Ver. 1.10 | - | ||
| Communication Speed | 125/250/500 kbps | 156/625 kbps 2.5 M / 5 M / 10 Mbps | 750 kbps | ||
| Configuration File*2 | EDS file | CSP + file | - | ||
| I/O Occupation Area (No. of Inputs/No. of Outputs) | 16/16 | 0/16 | 32/32 (1 station, remote I/O stations) | SCS1: 0/16 SCS2: 0/8 | |
| Power Supply Voltage | For Control | 11 V DC to 25 V DC | 15 to 30 V DC | 14 V DC to 26.4 V DC | |
| For Valve | 24 V DC +10%/-5% | ||||
| Output Specifications | Output Format | Sink/NPN (positive common) | |||
| Number of Outputs | 16 points | SCS1: 16 points SCS2: 8 points | |||
| Connection Load | SMC solenoid valve 24 V DC, 2.1 W or less with surge voltage suppressor circuit | ||||
| Output if Communication Error | Clear | Hold/Clear (Switch setting) | Clear | Hold/Clear (Switch setting) | |
| Standards | CE marking | ||||
| Weight | EX120: 110 g or less, EX121: 140 g or less, EX122: 130 g or less | ||||
| Accessories | Communication connector 1 pc., power supply connector 1 pc. | - | |||
| Model | EX12□-SUH1 | EX12□-SCM1 | EX12□-SCM3 | |
|---|---|---|---|---|
| Communication Specifications | Protocol Name | Made by NKE Fieldbus H System | CompoNet | |
| Communication Speed | 29.4 kbps | 93.75 kbps/1.5 Mbps/3 Mbps/4 Mbps | ||
| Configuration File | - | EDS file*1 | ||
| I/O Occupation Area (No. of Inputs/No. of Outputs) | 0/16 | |||
| Power Supply Voltage | For Control | 24 V DC ±10% (Common power supply) | 14 V DC to 26.4 V DC | |
| For Valve | 24 V DC +10%/-5% | |||
| Output Specifications | Output Format | Sink/NPN (positive common) | Sink/NPN (positive common) | Source/PNP (Negative common) |
| Number of Outputs | 16 points | |||
| Connection Load | SMC solenoid valve 24 V DC, 2.1 W or less with surge voltage suppressor circuit | |||
| Output if Communication Error | Clear | Hold/Clear (setting via network) | ||
| Standards | - | CE marking | ||
| Weight | EX120: 110 g or less EX121: 140 g or less EX122: 130 g or less | EX120: 100 g or less EX121: 120 g or less EX122: 110 g or less (including accessories) | ||
| Accessories | - | Power supply connector (EX9-CP2) 1 pc.*2 | ||
(Unit: mm)

EX120-SDN1(-X26) dimensional drawing
(Unit: mm)

EX120-SMJ1, SCS□, SUH1 dimensional drawing
(Unit: mm)

EX120-SCM□ dimensional drawing
(Unit: mm)

EX121-SDN1(-X26) dimensional drawing
(Unit: mm)

EX121-SMJ1, SCS□, SUH1 dimensional drawing
(Unit: mm)

EX121-SCM□ dimensional drawing
(Unit: mm)

EX122-SDN1(-X26) dimensional drawing
(Unit: mm)

EX122-SMJ1, SCS□, SUH1 dimensional drawing
(Unit: mm)

EX122-SCM□ dimensional drawing
| Part Number |
|---|
| EX122-SCS1 |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Valve Interface | Communication Protocol | Output Format |
|---|---|---|---|---|---|---|---|
MYR 1,937.03 | 1 Piece(s) | 21 Day(s) | Plug-in DIN rail mounting | OMRON CompoBus/S (16 output) | Sink/NPN (Positive common) |
Loading...
| Type Details | Solenoid |
|---|
Please check the type/dimensions/specifications of the part EX122-SCS1 in the Fieldbus System (for Output), EX120/121/122 Series series.
| Part Number |
|---|
| EX120-SCS2 |
| EX120-SDN1 |
| EX120-SMJ1 |
| EX122-SCS2 |
| EX122-SDN1 |
| EX122-SMJ1 |
| Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Valve Interface | Communication Protocol | Output Format |
|---|---|---|---|---|---|---|---|
MYR 1,689.83 | 1 Piece(s) | 21 Day(s) | Plug-In | OMRON CompoBus/S (8 output) | Sink/NPN (Positive common) | ||
MYR 2,369.15 | 1 Piece(s) | 14 Day(s) or more | Plug-In | DeviceNet (16 input/16 output) | Sink/NPN (Positive common) | ||
MYR 1,115.56 | 1 Piece(s) | 14 Day(s) or more | Plug-In | CC-Link | Sink/NPN (Positive common) | ||
MYR 1,689.83 | 1 Piece(s) | 21 Day(s) | Plug-in DIN rail mounting | OMRON CompoBus/S (8 output) | Sink/NPN (Positive common) | ||
MYR 2,369.15 | 1 Piece(s) | 14 Day(s) or more | Plug-in DIN rail mounting | DeviceNet (16 input/16 output) | Sink/NPN (Positive common) | ||
MYR 1,115.56 | 1 Piece(s) | 14 Day(s) or more | Plug-in DIN rail mounting | CC-Link | Sink/NPN (Positive common) |
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy