General-purpose Relays (Part Numbers)

General-purpose Relays

Click this image to zoom it.

Move the mouse over the image to zoom

Product Overview
● General-purpose relays are devices that receive input signals and output electrical signals to open or close circuits.
● Available in a wide variety of types, suitable for multiple control methods and for use as relays inside control panels, with a maximum load of 15 A.
Dimensional Drawing
■ Relay
· Dimension Diagram
Sensor Application ExampleSensor Application Example
Note: Pin configurations may vary slightly depending on the model.
Sensor Application Example 
· Internal Connection Diagram (Bottom View)
Sensor Application ExampleSensor Application ExampleSensor Application ExampleSensor Application Example
E-NRN4ZE-NRN2ZE-NRP2ZE-NRP1Z
Note: The input terminal has positive and negative poles. Please make sure to connect them correctly.

■ Relay socket
· Dimension Diagram
Sensor Application Example
Note: The appearance may vary slightly depending on the specifications.
Specification Table
ModelLoadContact configurationA1 (pin height)B1Surge protectionIndicator lightCertification
RelaySet (relay + relay socket)Rated current*1Rated voltage*1mmmm
E-NRN4ZL-5A-DC24E-NRN4ZL-5A-DC24-SET5A240 V AC/28 V DC4C6.336.5NoYesRelay: UL CCC CE
Relay socket: UL CE
E-NRN2ZL-6.5 A-DC24E-NRN2ZL-6.5 A-DC24-SET6.5 A2C6.336.5
E-NRP2ZL-10A-DC24E-NRP2ZL-10A-DC24-SET10A2C6.536.3
E-NRP1ZL-15A-DC24E-NRP1ZL-15A-DC24-SET15A1C6.536.3
E-NRN4ZD-5A-DC24E-NRN4ZD-5A-DC24-SET5A4C6.336.5Yes
E-NRN2ZD-6.5 A-DC24E-NRN2ZD-6.5 A-DC24-SET6.5 A2C6.336.5
E-NRP2ZD-10A-DC24E-NRP2ZD-10A-DC24-SET10A2C6.536.3
E-NRP1ZD-15A-DC24E-NRP1ZD-15A-DC24-SET15A1C6.536.3

· Performance parameters
ModelE-NRN4Z*-5A-*E-NRN2Z*-6.5 A-*E-NRP2Z*-10A-*E-NRP1Z*-15A-*
Rated load current5A6.5 A10A15A
Operating time*1≤ 15 ms≤ 20 ms
Reset time*1≤ 10 ms≤ 20 ms
Input (operating coil)*1Rated voltageVDC24
Coil resistanceΩ640
Operating voltageV≥ DC18
Reset voltageV≤ DC2.4
Maximum allowable voltageVDC26.4
PowermWApprox. 900
Contact materialSilver alloy
Maximum switching frequencyMechanical18,000/h
Rated load1,800/h
Contact resistance*2≤ 100
VibrationMalfunctionVibrate in three directions for 5 minutes, malfunction not exceeding 1 ms (amplitude 1 mm, 10–55 Hz)
Vibration durabilityVibrate in three directions for 2 hours, no structural failure (amplitude 1 mm, 10–55 Hz)
ShockMalfunctionThree shocks applied in three directions, contact malfunction does not exceed 1 ms (maximum acceleration 98 m/s2, duration 11 ms)
Shock resistanceThree shocks applied in three directions, no structural damage (maximum acceleration 98 m/s2, duration 6 ms)
Insulation strengthBetween contacts1000 V AC, 1 min
Between coil and contacts1500 V AC, 1 min
Insulation resistance≥ 100
Service lifeMechanical10,000 times≥ 1,000
Electrical*310,000 times≥ 10
Note:
 *1. Coil temperature is +23°C, resistive load
 *2. Measurement conditions: 6 V DC 1 A voltage drop method
 *3. Test conditions: rated load, frequency 900 cycles/h
Sensor Application Example
(Set product)
· Specifications Table
ModelABCMounting hole dimensionsMounting methodTerminal screwFinger protectionCertification
Set
(relay + relay socket)
Relay socketDFE
mmmmmmmmmmmm
E-NRN4ZL-5A-DC24-SETE-NSN4Z-7A75.630.829.422594.2DIN rail
screw mounting
M3YesUL CE
E-NRN4ZD-5A-DC24-SET
E-NRN2ZL-6.5 A-DC24-SETE-NSN2Z-10A75.630.822.415594.2M3
E-NRN2ZD-6.5 A-DC24-SET
E-NRP2ZL-10A-DC24-SETE-NSP2Z-16A7832.42819684.5M3.5
E-NRP2ZD-10A-DC24-SET
E-NRP1ZL-15A-DC24-SET
E-NRP1ZD-15A-DC24-SET
Product Features
● Rated load options from 5 A to 15 A to meet the needs of different application scenarios.
● All models come standard with an LED operation indicator; built-in surge protection type is also available.
● Optional relay set (relay + relay socket) for complete selection.
● High electrical durability helps reduce maintenance frequency.
● Certified by UL, CE, and CCC.
Precautions
· The input terminal has polarity; be sure to connect it correctly.
· There is no installation direction restriction, but please avoid installation methods where the contact movement direction is easily affected by vibration or impact.
· Do not perform operations while powered.
· Operating environment: -40°C to +85°C, no freezing or condensation, humidity 45–85%.
· The set requires self-assembly. The relay socket comes standard with finger protection. Please use Y-type terminals for connection.

Part Number 

CAD Data download and 3D preview are not available because the part number has not yet been determined.

  • *In order to open the CAD Data download and 3D preview screen, the part number must be fixed.
  • Please confirm the part number from "Specification / Dimension"on the left side, and then perform the CAD Data Download / 3D Preview operation.
Loading...
Part Number
E-NRN2ZD-6.5A-DC24
E-NRN2ZD-6.5A-DC24-SET
E-NRN2ZL-6.5A-DC24
E-NRN2ZL-6.5A-DC24-SET
E-NRN4ZD-5A-DC24
E-NRN4ZD-5A-DC24-SET
E-NRN4ZL-5A-DC24
E-NRN4ZL-5A-DC24-SET
E-NRP1ZD-15A-DC24
E-NRP1ZD-15A-DC24-SET
E-NRP1ZL-15A-DC24
E-NRP1ZL-15A-DC24-SET
E-NRP2ZD-10A-DC24
E-NRP2ZD-10A-DC24-SET
E-NRP2ZL-10A-DC24
E-NRP2ZL-10A-DC24-SET
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipContact Configuration Contact rated current (minimum value for AC and DC)
(A)
Type Diode type Mounting method

MYR 17.29

1 Piece(s)Available 6 Day(s) 2c6.5Relay unitBuilt-in diode surge protectionSocket type

MYR 20.71

1 Piece(s)Available 6 Day(s) 2c6.5Set (relay + relay socket)Built-in diode surge protectionDIN rail / screw

MYR 16.88

1 Piece(s)Available 6 Day(s) 2c6.5Relay unitStandard typeSocket type

MYR 20.29

1 Piece(s)Available 6 Day(s) 2c6.5Set (relay + relay socket)Standard typeDIN rail / screw

MYR 17.74

1 Piece(s)Available 6 Day(s) 4c5Relay unitBuilt-in diode surge protectionSocket type

MYR 22.74

1 Piece(s)Available 6 Day(s) 4c5Set (relay + relay socket)Built-in diode surge protectionDIN rail / screw

MYR 17.33

1 Piece(s)Available 6 Day(s) 4c5Relay unitStandard typeSocket type

MYR 22.32

1 Piece(s)Available 6 Day(s) 4c5Set (relay + relay socket)Standard typeDIN rail / screw

MYR 18.65

1 Piece(s)Available 6 Day(s) 1c15Relay unitBuilt-in diode surge protectionSocket type

MYR 25.16

1 Piece(s)Available 6 Day(s) 1c15Set (relay + relay socket)Built-in diode surge protectionDIN rail / screw

MYR 18.22

1 Piece(s)Available 6 Day(s) 1c15Relay unitStandard typeSocket type

MYR 23.17

1 Piece(s)Available 6 Day(s) 1c15Set (relay + relay socket)Standard typeDIN rail / screw

MYR 18.65

1 Piece(s)Available 6 Day(s) 2c10Relay unitBuilt-in diode surge protectionSocket type

MYR 25.16

1 Piece(s)Available 6 Day(s) 2c10Set (relay + relay socket)Built-in diode surge protectionDIN rail / screw

MYR 18.22

1 Piece(s)Available 6 Day(s) 2c10Relay unitStandard typeSocket type

MYR 23.17

1 Piece(s)Available 6 Day(s) 2c10Set (relay + relay socket)Standard typeDIN rail / screw

Loading...

  1. 1
Brand Introduction
Since its establishment in Japan in 1963, MISUMI Corporation has been committed to providing customers with a wide variety of high-quality parts for FA (Factory Automation), mold components, electronic parts, tools, and consumables quickly and accurately. By independently compiling product catalogs and establishing a direct sales marketing system, we have created a low-cost business model. Each year, we develop product plans based on customer feedback and requests, and continuously develop MISUMI brand products with a high level of quality.

Basic Information

Coil rated voltage (DC)(V) 24

Frequently asked question (FAQ)

Question: 1. What are the external reasons why the relay does not operate after being energized?
Answer: (1) Applying excessive voltage to the relay coil can cause the coil to break.
(2) If the voltage applied to the relay coil is insufficient, the relay will not operate.
(1) The voltage applied to the coil does not reach the minimum operating voltage.
(2) The voltage in the circuit may drop below the minimum operating voltage due to the operation of large machines or the use of long-distance wiring.
(3) If the ambient temperature is too high, the resistance of the relay coil increases, causing the required operating voltage to rise. As a result, the originally applied rated voltage is no longer sufficient to drive the relay.