Product Overview
● The relay module is a device used to receive input signals and output power signals, enabling the opening and closing of circuits.
● The relay module is also known as a terminal relay or relay module.
● It serves as an intermediate relay module for connecting controllers such as PLCs and loads such as solenoid valves.
● The relay module functions as a signal amplifier and isolator in the circuit.
Dimensional Drawing
■ Dimensional drawings
Dimension diagram
E-MR-5A-4
Dimension diagram
E-MR-5A-8

■ Wiring diagram
E-MR-5A-4 E-MR-5A-8
Wiring diagram Wiring diagram

Note: Be sure to connect the positive and negative terminals correctly at the input.


■ Accessory dimension diagram
■ Accessory dimension diagram
Shorting bar (E-MR-5A-4)
■ Accessory dimension diagram
Shorting bar (E-MR-5A-8)
Specification Table
■ Specification table
ModelLengthWidthHeightNumber of polesWeightEquipped relayContact configurationMounting methodTerminal screwIndicator lightAccessoriesCertification
mmmmmmmmgSpecificationsTightening torque
E-MR-5A-476.438.232.8480Omron
G5NB-1A-E
1a × 4DIN railM30.6 N⋅mYesShorting bars (2 pieces)CE
E-MR-5A-876.438.263.681601a × 8

■ Performance parameters (single relay)
ModelE-MR-5A-4/E-MR-5A-8Diagram
Input
(operating coil)*1
Rated voltageVDC24
Rated currentmA8.3
Coil resistanceΩ2880
Operating voltageV≥ DC18
Reset voltageV≤ DC2.4
Maximum allowable voltageVDC40
PowermWApprox. 200
Output terminal
(switch section)
Contact materialAg alloy
Rated load voltageVAC250/DC30
Rated load currentA5
Contact resistance*2≤ 100
Operating timems≤ 10
Reset timems≤ 10
Insulation resistance*3≥ 1,000
Service lifeMechanical10,000 times≥ 500
Electrical*410,000 times≥ 10

Note *1: 1.1. The rated current and coil resistance values refer to the values at a coil temperature of +23°C, with a tolerance of ±10%.
   1.2. The operating characteristics refer to the values at a coil temperature of +23°C.
   1.3. The maximum allowable voltage refers to the maximum value within the permissible voltage range for the relay coil operating power supply, not the continuous allowable voltage.
   1.4. The rated current includes the LED current of the module.
 *2. Measurement conditions: 5 V DC 1 A voltage drop method
*3. Measurement conditions: 500 V DC
*4. Test conditions: rated load, frequency 1800 cycles/h

Product Features
● Uses Omron miniature relays (G5NB-1A-E) with a compact design to save space.
● Uses DIN rail mounting method.
● Each relay has an independent coil and independent contacts for one-to-one control, supporting PLC output (NPN/PNP).
● Includes shorting bars for easy common wiring.
● The actuator coil terminal is equipped with an LED operation indicator, flyback protection, and surge protection.
● The relay uses a pull-release latch for easy maintenance.
Precautions
· The input terminal has polarity; be sure to connect it correctly.
· Before connecting, please confirm the device specifications.
· Do not operate while powered.
· Operating environment: -40°C to +80°C, non-vacuum, non-freezing conditions, 35–85% RH
Installation Method
Installation Method
Installation Method
Part Number
E-MR-5A-8
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipNumber of positions Weight
(g)

MYR 72.16

1 Piece(s)Available 6 Day(s) 8160

Loading...

  1. 1
Brand Introduction
Since its establishment in Japan in 1963, MISUMI Corporation has been committed to providing customers with a wide variety of high-quality parts for FA (Factory Automation), mold components, electronic parts, tools, and consumables quickly and accurately. By independently compiling product catalogs and establishing a direct sales marketing system, we have created a low-cost business model. Each year, we develop product plans based on customer feedback and requests, and continuously develop MISUMI brand products with a high level of quality.

Basic Information

Rated voltage DC(V) 24 Rated current(mA) 8.3 Installation Method DIN rail
Input-side connector Terminal block Output-side connector Terminal block Output load voltage(V) AC250/DC30
Output load current(A) 5 Operation indicator LED Terminal screw M3

Please check the type/dimensions/specifications of the part E-MR-5A-8 in the Relay Modules series.

Frequently asked question (FAQ)

Question: What are the reasons why the contacts do not operate after the relay is energized?
Answer: 1. Excessive voltage applied to the relay coil causes the coil to break. 2. Insufficient voltage applied to the relay coil causes the relay to fail to operate. 3. The voltage applied to the coil does not reach the minimum operating voltage (≥ 18 V DC). 4. Due to operation of heavy load equipment or use of long-distance wiring, the circuit voltage may drop and fail to reach the minimum operating voltage. 5. Due to excessively high ambient temperatures, the resistance of the relay coil increases, causing the operating voltage required to drive the relay to rise. As a result, the originally applied rated voltage is no longer sufficient to operate the relay.
Question: Why do the contacts operate after the relay is energized, but the operation indicator does not light up?
Answer: The leads of the LED may break due to vibration, impact, or similar reasons.